Advertisement

Error code
D2AEH
D2AFH
D2B0H
D501H
D502H
D529H and
D52AH
D52BH and
D52CH
D62DH
D62EH
Downloaded from
ManualsNet.com
Error
Target station No. error in transient
transmission
Target station No. error in transient
transmission
Transient transmission failed
Communication LSI failure
MAC address error
RAM failure
Communication LSI failure
Data link start failed
Master station lost
search engine
• The head module received transient data addressed to a different network.
Check the network number and target station number, and retry the
operation.
• Check if the routing parameters are correctly set.
• Transient data transmission addressed to the own station was requested.
Check the network number and target station number, and retry the
operation.
• Check if the routing parameters are correctly set.
• Check if the switching hub and the cables at the request source are
connected properly.
• Connect the cable to the other port on the request source, and retry the
operation.
• Reduce the frequency of transient transmission, and retry the operation.
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures to
reduce noise.
• Execute a unit test for the head module. If a failure occurs again, the
possible cause is a hardware failure of the head module. Please consult
your local Mitsubishi representative.
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures to
reduce noise.
• Execute a unit test for the head module. If a failure occurs again, the
possible cause is a hardware failure of the head module. Please consult
your local Mitsubishi representative.
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures to
reduce noise.
• Execute a unit test for the head module. If a failure occurs again, the
possible cause is a hardware failure of the head module. Please consult
your local Mitsubishi representative.
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures to
reduce noise.
• Execute a unit test for the head module. If a failure occurs again, the
possible cause is a hardware failure of the head module. Please consult
your local Mitsubishi representative.
Data link start failed due to any of the following causes.
Eliminate the error cause, and retry the operation.
• Station number not set
• Head module error
• More than one master station
• Station type mismatch
• Master station lost
• Own station No. out of range
• Station No. already in use (own station)
• Own station reserved
• Parameter error
• Parameter communication in progress
• Parameters not received (master station only and no slave station exists)
• Link stop command
Communications cannot be performed with the master station. Check
whether the cables are connected properly.
CHAPTER 11 TROUBLESHOOTING
Action
11
107