4.7.4 Replacement of Gas Heat Exchanger – AK1840
! Close gas supply/ isolate 230V supply.
! Remove cover, blown air fan, PCBs, solenoid, fan motors and burner assembly.
- unscrew the 2 flat head screws
1
securing the rear casing.
- slide out the unit and free from the casing. Example
4
shown is gas and electric (electric element wiring can be
seen).
FINAL CHECKS: Full commissioning to include combustion analysis and gas soundness test

4.8 Gas Overheat (O/H) Thermostat check and replacement - AK1854

The overheat thermostat can be checked at the Heat Air Room Heater without DC power being
supplied to the unit by measuring its continuity. The O/H thermostat should normally be in the closed
condition when less than 150
The O/H stat is accessible once the Gas Heat Exchanger has been removed, see previous chapter, and can be checked
directly at the device as shown or on the connectors when removed from the PCB as indicated. Testing on the device is
preferable as it eliminates potential faults in the wiring and connections. To access the PCB please see Chapter 4.5. If the
O/H stat is faulty (no continuity), follow the steps below to fit the replacement.
- with cover removed, use a T20
1
screwdriver to remove securing
screw.
FINAL CHECKS: Full commissioning to include combustion analysis and gas soundness test
This data is confidential to Brunswick
Munster Simms Engineering Ltd., 2 Enterprise Road, Bangor, Co Down, BT19 7TA, U.K. – Northern Ireland
fax.: +44 (0)2891 466 421
- slacken the 2 posi screws
2
at the hot air outlet, but do
not remove entirely
C. When in cold condition follow the steps shown below.
°
- unhinge the bracket, prise from
2
location and lift wires over
securing rivet.
Heat Air Room Heater
info@whalepumps.com
- If the heat exchanger does not slide
3
out by hand then use a removal tool to
firmly tap out exchanger.
- when replacing unit ensure no cables are
5
snagged between unit and casing as above
- slide stat through gap in the bracket
3
hinges. Replace with new O/H stat
by reversing steps & secure bracket.