Bars: Combustion Air Fault; Bars: Room Heater Issues; All Bars: Multiple Faults - Whale Heat Air SL5511Ux How-To Manual

Table of Contents

Advertisement

tel.: +44 (0)2891 270 531
4.1.1.4 – 4 Bars: Combustion air fault
Process
Try to clear lockout (see 4.1.1)
Check external corrugated flues for:
o
Constant downhill slope on flues
o
Damage
o
Low points/kinks where condensate can gather
o
Obstructions in the flues
Internal Heater checks (Service Engineer Only)
o
Check fan wheels and combustion circuit are free from
debris
o
Check fan runs when heating is turned on
o
Check if the current draw is constant when lit/running –
aiming for approx. 7.9 Amps
4.1.1.5 – 5 Bars: Room Heater issues
Process
Try to clear lockout (see 4.1.1)
NOTE:
- Check all Flues.
- Check Thermistor is fully engaged in PCB connection.
Replace PCB
4.1.1.6 – All Bars: Multiple faults
Process
Try to clear lockout (see 4.1.1)
NOTE:
- Can also occur when 2 or more lockout clearing attempts have been
unsuccessful
Replace PCB
Heat Control Panel only: All bars are lit except for the last bar.
Try to clear lockout (see 4.1.1)
This data is confidential to Brunswick
Munster Simms Engineering Ltd., 2 Enterprise Road, Bangor, Co Down, BT19 7TA, U.K. – Northern Ireland
fax.: +44 (0)2891 466 421
Heat Air Room Heater
info@whalepumps.com
Actions
This should cure most simple
problems.
Clear obstructions or water build-
up if present.
If the fan does not run when
heating is demanded, the fan
motor may be jammed, and need
replaced – Service engineer only.
Actions
This should cure most simple
problems.
Carry out continuity test by
Service Engineer.
Change the PCB by Service
Engineer.
Actions
This should cure most simple
problems.
Allow 5-10mins for unit to cool
and follow reset procedure.
Change the PCB by Service
Engineer.
This should cure most simple
problems.
Replace panel if persists
Page
|
13 of 34
www.whalepumps.com

Advertisement

Table of Contents
loading

Table of Contents