Thermo King T-1000R Series Maintenance Manual page 80

Hide thumbs Also See for T-1000R Series:
Table of Contents

Advertisement

L1, L2 and L3 respectively. Operating power from
12 to 24 volts is supplied to the module via the 8
wire and CH wire.
When the voltage sensed rises above 165 volts
AC and all three phases are present, the module
ER wire will output 12 volts DC after the
conditions exist for 2 to 4 seconds. This signal
informs the microprocessor that electric standby
operation is possible. If the voltage drops below
160 volts AC or a phase is lost, the ER output is
turned off after the condition exists for 3 seconds.
The module continues to monitor the power and
the module ER wire will again output 12 volts DC
within 2 to 4 seconds after the voltage rises above
165 volts AC and all three phases are present.
If phase orientation is L1, L2, L3 the 7EB wire
will output voltage to energize the appropriate
phase rotation contactor MCA. If phase
orientation is L1, L3, L2 the 7EC wire will output
voltage to energize the appropriate phase rotation
contactor MCB. The 7EB and 7EC wires are
interlocked to prevent both phase contactors from
being energized at once.
If the SP input is grounded, the module will now
be set for single-phase operation. In this case only
the Brown and Gray wires are used and the Black
wire is taped off.
Connections to the module are shown in the tables
below.
Power Connections
Input
Description
8
Nominal 12 volt DC power to the phase
select module
CH
Chassis ground
Inputs
Input
Description
L1
This Brown wire supplies standby power L1
to the phase select module.
L2
This Gray wire supplies standby power L2
to the phase select module.
L3
This Black wire supplies standby power L3
to the phase select module.
7EA
If 12 volts DC is supplied, then output 7EB
or 7EC will be at 12 volts DC
SP
If this wire is connected to chassis ground
the module will operate in single-phase
mode.
SP-
This is an internal ground for the module. If
GND
SP-GND is jumpered to SP then the
module will be set to operate on single
phase.
Outputs
Output
Description
7EB
If phase orientation is L1, L2, L3 then this
wire will provide 12 volts DC to energize
the appropriate phase rotation contactor
MCA. The 7EC wire is interlocked to
prevent both phase contactors from being
energized at once.
7EC
If phase orientation is L1, L3, L2 then this
wire will provide 12 volts DC to energize
the appropriate phase rotation contactor
MCB. The 7EB wire is interlocked to
prevent both phase contactors from being
energized at once.
ER
This wire will output 12 volts DC to the
microprocessor 2 to 4 seconds after the
voltage rises above 165 volts AC and all
three phases are present. If the voltage
drops below 160 volts AC or a phase is
lost and the condition remains for 3
seconds, the output is turned off. The
module continues to monitor and will
again output 12 volts DC 2 to 4 seconds
after the power returns to normal (voltage
rises above 165 volts AC and all three
phases are present).
Electrical Maintenance
79

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

T-600rT-800r

Table of Contents