11� Technical specifications
IS 3180
IS 3360 / IS 3360 MX IS 345
Dimensions
Surface-mounted installation, round Ø
(L × W × H)
Surface-mounted installation, square
Concealed installation, round Ø
Concealed installation, square
Output
Incandescent / halogen lamp load
Fluorescent lamps, electronic ballast
Fluorescent lamps, uncorrected
Fluorescent lamps, series-corrected
Fluorescent lamps, parallel-corrected
Low-voltage halogen lamps
LED < 2 W
2 W < LED < 8 W
LED > 8 W
Capacitive load
Mains power
220-240 V, 50 / 60 Hz max. 2.5 mm
supply
Angle of
180° with 90°
360° with 180°
coverage
angle of perture
angle of aperture
Reaches
Basic
IS 3360
setting 1:
max. 20 m
max. 8 - 20 m
tangential;
tangential;
temperature
temperature
stabilised
stabilised
IS 3360 MX
Basic
max. 18 m;
temperature
setting 2:
max. 4-8 m:
stabilised
temperature
+ precision
stabilised
adjustment
+ precision
using shrouds
adjustment by
repositioning
the lens and
using shrouds
Detection levels
7
11
Switching zones 448
1416
Time setting
5 s - 15 min + pulse mode (approx. 2 s)
Twilight setting
2-1000 lux + teach mode
Manual override
selectable (4 h)
(permanent light)
IP rating
Surface-mounted: IP 54
Temperature
-20°C to +50°C
zone
IS 345 MX
126 ×  65 mm
95 ×  95 ×  65 mm
124 ×  78 mm
94 ×  94 ×  78 mm
2000 W
1500 W
1000 VA
400 VA
400 VA
2000 VA
100 W
300 W
600 W
176 μF
2
180° with 45°
180° with 45°
angle of perture
angle of perture
max. 20 × 4 m
max. 30 × 4 m
(tangential),
(tangential)
max. 12 × 4 m
mounted at a
(radial);
height of 14 m;
temperature
temperature
stabilised
stabilised
+ precision
+ precision
adjustment
adjustment
using shrouds
using shrouds
5
5
280
120
Concealed: IP 20
34
12� Troubleshooting
Malfunction
Cause
No power at the sensor
n Fuse faulty, not
switched ON,
break in wiring
n Short circuit
Sensor will not switch ON
n Twilight setting set to
night-time mode during
daytime operation
n Bulb faulty
n Mains power switch
OFF
n Fuse faulty
n Detection zone not
properly targeted
Sensor will not switch OFF
n Continuous movement
in the detection zone
n Light being operated
is located in detection
zone and keeps switch-
ing ON as a result of
temperature change
n Light being operated
is in manual override
mode (LED ON)
Sensor keeps switching
n Light being operated is
ON/OFF
located in the detec-
tion zone
n Animals moving in the
detection zone
Sensor reach
n Change in ambient
change
temperatures
Remedy
n New fuse, turn ON
power switch, check
wiring with voltage tester
n Check connections
n Adjust setting
n Change bulb
n Switch ON
n Fit new fuse, check
connection if necessary
n Readjust
n Check zone, adjust or fit
shrouds if necessary
n Change detection zone
or fit shrouds
n Deactivate
manual override
n Change zone
or fit shrouds,
increase distance
n Change detection zone
or fit shrouds
n Use shrouds to define
detection zone precisely