Communications
RS-485 Modbus (standard)
The standard RS-485 connection is routed to the DIN rail from the main PCB as shown in
Figure 5-30.
Copper Ethernet (optional)
Copper Ethernet supports the Modbus protocol with DNP 3.0 or IEC 61850. With this
equipment, only shielded cable should be used to meet the required EMC standards. If an
optional communication channel has been specified, there will be an extra module on
the Intellix™ BMT 330 motherboard as shown in Figure 5-31. This module supports
MultiMaster communications.
Figure 5-31: Copper Ethernet
For more details on how to configure the optional communication module, see Appendix
E.
The copper-based channel requires a cat 5e Ethernet cable and a clamp-on ferrite
(included in the Installation kit, see Appendix B). This cable must enter the cabinet
through one of the available cable glands and must be routed to the communication
module. The ferrite must be added to the Ethernet cable with 3 loops (4 passes) inside
the cabinet close to where the cable exits the cabinet.
MA-017 – BMT 330 Installation Manual – Rev 3.3
4-Mar-22
Page 30 of 69