Bulk Gas Plumbing Information
IMPORTANT:
An installer-supplied safety shut-off valve MUST be installed at the gas supply
line connection point for the grill. The valve should be easily accessed and located between 3
and 20 feet away from the grill.
All gas connections should be made by a qualified technician. The installation and all installer-
supplied parts must conform to local codes. In the absence of local codes, the installation and all
parts should conform to the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or Natural Gas and
Propane Installation Code, CSA B149.1. Cooktops to be connected to a fixed fuel piping system
must use rigid pipe, semi-rigid tubing, and/or a connector that complies with the Standard for
Connectors for Outdoor Gas Appliances and Manufactured Homes, ANSI Z21.75/CSA 6.27.
IMPORTANT:
Always close gas supply shut-off valve before disconnecting the grill gas supply hose.
All pipe sealants must be an approved type.
IMPORTANT:
Diameter and length of the gas supply pipe may limit the pressure and BTU delivery
of gas to the grill. The installer must ensure proper delivery to the grill or it will not operate properly.
The appliance must be disconnected from the gas supply piping system during any pressure testing
of that system at pressures in excess of 1/2 psi (3.5 kPa).
During any pressure testing of the gas supply piping system at test pressures equal to or less than
1/2 psi (3.5 kPa), the appliance must be isolated from the system by closing the supply shut-off valve.
10