Required ventilation for built-in LP-gas cylinder structures:
An enclosure for an LP-gas cylinder shall be ventilated by openings at both the upper and lower levels of the
enclosure (See Figure 2). The effectiveness of the opening(s) for purposes of ventilation shall be determined
with the LP-gas supply cylinder in place. This shall be accompanied by one of the following:
1.
One side of the enclosure shall be completely
open; or
2.
For an enclosure having four sides, a top and a
bottom:
a.
At least two ventilation openings shall be
provided in the side walls of the enclosure,
located within 5 in (217 mm) of the top of the
enclosure, equally sized, spaced at a minimum
of 90 degrees (1.57 rad), and unobstructed. See
Figure 2. The opening(s) shall have a total free
area of not less than 1 in
stored fuel capacity.
b.
Ventilation opening(s) shall be provided at floor
level of the enclosure and shall have a total free
area of not less than 1/2 in
stored fuel capacity. If ventilation openings at
floor level are in a side wall, there shall be at
least two openings. (See Figure 2) The bottom
of the openings shall be 1 in (25.4 mm) or less
from the floor level and the upper edge no
more than 5 in (127 mm) above the floor level.
The openings shall be equally sized, spaced at
a minimum of 90 degrees and unobstructed.
c.
Every opening shall be a minimum of a 1/8 in
(3.2 mm) diameter.
d.
Ventilation openings in side walls shall not
communicate directly with other enclosures of
the outdoor cooking gas appliance.
e.
A door on the enclosure to gain access to the
cylinder is acceptable, provided it is non locking
and can be opened without the use of tools.
DANGER:
A. Do not store a spare LP-gas cylinder under or near this appliance;
B. Never fill the cylinder beyond 80 percent full; and
C. If instructions A and B are not followed exactly, a fire causing death or
serious injury may occur.
+1.800.868.1699
2
2
/lb (14.2 cm
/kg) of
2
/lb (7.1 cm
2
/kg) of
3.
Some means of retention (chain, bracketry, cut-
out) must be used to hold cylinder in place inside
enclosure.
4.
There shall be a minimum clearance of 2 in (50.8
mm) between the floor of the LP-gas cylinder
enclosure and the ground.