Segment 6:
1 = Enable 2 wire smoke.
2 = Reserved.
3 = Enable for Zone Activity in Hours (not Days)
4 = Enable Daylight Savings Time (DST)
5 = Reserved
6 = On to disable Clean Me report (Clean Me report is enabled at default)
7-8 = Reserved.
Segment 7:
Reserved
L
LOCATION 38 - SWINGER SHUTDOWN COUNT
Location 38 contains the number of trips during an arming cycle that the NX8 will allow before bypassing a zone.
The count determination is described in the feature definitions beginning on page 3.
installations, this feature shall be disabled.
.
L
LOCATION 39 - KEYPAD SOUNDER CONTROL (1 segment, feature selection data)
1 - On if keypad sounds for ATelephone Line Cut@ when the system is armed.
Segment 1:
2 - On if keypad sounds for ATelephone Line Cut@ when disarmed.
3 - On if keypad sounds upon AC Power Failure.
4 - On if keypad sounds when a Low Battery is detected.
5 - On if keypad sounds during Cross Zone trip time.
6 - On if keypad sounds for zone and box tampers.
7 - Reserved.
8 - On if keypad sounds for expander trouble (required for UL installations).
L
LOCATION 40 - SYSTEM TIMERS (14 segments, numerical data)
Location 40 contains the duration of various system timing functions. Example: If you desire the duration of the
Dynamic Battery Test to be 30 minutes, you should program [3]-[0]-[r] in segment 1 of this location. The [3]-[0]
is the number of minutes, and the [r] stores the data and moves to the next segment of this location.
Segment 1 - Dynamic Battery Test duration in minutes 0-255 minutes ("0" = no test)
Segment 2 - AC Fail report delay in minutes 0-255 minutes.
Segment 3 - Power Up Delay in seconds 0-60 seconds ("0" = no power up delay).
Segment 4 - Siren Time in minutes 1-255 minutes.
Segment 5 - Telephone Line Cut delay in seconds 0-255 seconds ("0" = no TLM).
Segment 6 - Cross Zone time in minutes 0-255 ("0" = no cross zoning).
Segment 7 - Chime time in 50 mS (1/20th second) increments from 0-12 seconds ("0" = follows zone 255
latched).
Segment 8 - Dial delay in seconds 0-255 seconds ("0 " = no abort delay).
Segment 9 - Fire Alarm Verification time in seconds 120-255 seconds ("0" = no fire alarm verification).
NOTE: This feature is not approved for residential use in California
Segment 10 -Listen-In time in seconds 0-255 ("0" = no Listen-In time).
Segment 11 –Zone Activity Monitor feature timed in days 0 – 255 ("0" = disabled)
Segments 12-14 Reserved.
Note: The "Listen-In" feature cannot be enabled for UL Listed systems. The "Dynamic Battery
Test" feature cannot exceed four (4) hours. The dial delay shall be set to -0-.
LOCATION 41 - SPECIAL FEATURES (1 segment, feature selection data)
Segment 1:
1 -
On enables the 6-digit code option. If 6-digit option is enabled, all arm/disarm codes and the "Go To
Program Code" are 6 digits. If this option is enabled, the default user 1 code is [1]-[2]-[3]-[4]-[5]-[6].
NOTE: IF YOU ENABLE THIS OPTION, VERIFY THAT THE "GO TO PROGRAM CODE" IS A SIX-
DIGIT CODE BEFORE EXITING PROGRAMMING.
2 -
On requires code entry for [r]-[9]-[8] (perform call back download) and [r]-[9]-[9] (answer incoming
call for download) functions.
3 -
Enable Auto Cancel / Abort (Refer to feature definitions beginning on page 3)
4 -
Enable Walk-Test Mode (Refer to feature definitions beginning on page 3)
5-8
Reserved.
NX-8E CONTROL
NOTE: For UL
23