Description Of Parameter Settings - Delta Electronics VFD-M Series User Manual

High performance / low-noise micro-type ac motor drives
Table of Contents

Advertisement

Chapter 4 Parameters|

4.3 Description of Parameter Settings

This parameter can be set during operation.
Pr.00
Source of Frequency Command
Settings 00
01
02
03
04
Pr.01
Source of Operation Command
Settings 00
01
02
03
04
Refer to Pr.38 to Pr.42 for more details.
Pr.02
Stop Method
Settings 00
01
This parameter determines how the motor is stopped when the AC drive receives a valid stop
command.
1. Ramp: The AC drive decelerates the motor to Minimum Output Frequency (Pr.08) and
then stops according to the deceleration time set in Pr.11 or Pr.13.
2. Coast: The AC drive will stop the output instantly, and the motor will coast to stop.
4-20
Master Frequency determined by digital keypad. (LC-M02E)
Master frequency determined by 0 to +10 V input
Master frequency determined by 4 to 20mA input
Master frequency determined by RS-485 Communication port
Master frequency determined by potentiometer on digital keypad.
(LC-M02E)
Operation instructions determined by the Digital Keypad.
Operation instructions determined by the External Control Terminals.
Keypad STOP key is effective.
Operation instructions determined by the External Control Terminals.
Keypad STOP key is not effective.
Operation instructions determined by the RS-485 communication port.
Keypad STOP key is effective.
Operation instructions determined by the RS-485 communication port.
Keypad STOP key is not effective.
Ramp to stop
Coast to stop
Factory Setting: 00
Factory Setting: 00
Factory Setting: 00
Revision May 2008, ME14, SW V3.04

Hide quick links:

Advertisement

Table of Contents
loading