Note: The motor stop method is usually determined by the application or system requirements.
Pr.03
Maximum Output Frequency
Settings 50.00 to 400.0 Hz
This parameter determines the AC drive's Maximum Output Frequency. All the AC drive
analog inputs (0 to +10V, 4 to 20mA) are scaled to correspond to the output frequency range.
Pr.04
Maximum Voltage Frequency (Base Frequency)
Settings 10.00 to 400.0Hz
This parameter should be set according to the rated frequency as indicated in the motor
nameplate. Pr.04 and Pr.03 determine the volts per hertz ratio.
For example: if the drive is rated for 460 VAC output and the Maximum Voltage Frequency is set to
60Hz, the drive will maintain a constant ratio of 7.66 v/Hz. Setting of Pr.04 must be equal to or
greater than setting of Mid-Point Frequency (Pr.06).
Pr.05
Maximum Output Voltage (Vmax)
Settings 115V/230V series
460V series
575V series
This parameter determines the Maximum Output Voltage of the AC drive. The Maximum
Output Voltage setting must be smaller than or equal to the rated voltage of the motor as
indicated on the motor nameplate. Setting of Pr.05 must be equal to or greater than setting
of Mid-Point Voltage (Pr.07).
Revision May 2008, ME14, SW V3.04
Stops according
to deceleration
time
ON
OFF
Ramp
0.1 to 255.0V
0.1 to 510.0V
0.1 to 637.0V
Hz
Freq.
Motor
Speed
Time
Chapter 4 Parameters|
Free running
to stop
ON
OFF
Coast
Factory Setting: 60.00
Factory Setting: 60.00
Factory Setting: 220.0
Factory Setting: 440.0
Factory Setting: 575.0
Time
Unit: 0.1Hz
Unit: 0.1Hz
4-21