Appendix B Accessories|
B.5 Zero Phase Reactor (RF220X00A)
Dimensions are in millimeter.
Recommended Wire
Cable
Size
type
(Note)
AWG mm
≦10 ≦5.3
Single-
core
≦2 ≦33.6
≦12 ≦3.3
Three-
core
≦1 ≦42.4
Note: 600V Insulated Unshielded Cable.
Diagram A
Please wind each wire 4 times around the
core. The reactor must be put at inverter side
as close as possible.
R/L1
U/T1
Power
S/L2
V/T2
Supply
T/L3
W/T3
B-10
Qty.
Nominal
2
2
(mm
)
Diagram
1
≦5.5
Diagram
≦38
4
Diagram
1
≦3.5
Diagram
4
≦50
Zero Phase Reactor
MOTOR
Wiring
Diagram B
Method
Please put all wires through 4 cores in
series without winding.
A
Power
Supply
B
A
Note 1: The table above gives
B
approximate wire size for the zero phase
reactors but the selection is ultimately
governed by the type and diameter of
cable fitted i.e. the cable must fit through
the center hole of zero phase reactors.
Note 2: Only the phase conductors should
pass through, not the earth core or screen.
Note 3: When long motor output cables
are used, an output zero phase reactor
may be required to reduce radiated
emissions from the cable.
Zero Phase Reactor
R/L1
U/T1
S/L2
V/T2
T/L3
W/T3
Revision May 2008, ME14, SW V3.04
MOTOR