Panel Mounting and Installation - Class II
Install the meters in a suitable protective electrical control enclosure according to local wiring
regulations. See specifications for maximum allowable temperature in enclosure. Allow
adequate air circulation.
Installing into front of panel
Remove the two rear bracket
screws and safely store them
and the U-Bracket for later fitting.
Bracket screws
U-Bracket
Securing into the panel
Re-fit the U-Bracket and tighten the bracket
screws to firmly clamp the meter in place.
Check that the gasket is evenly pinched
between the meter's front bezel and the
enclosure front
Ventilation
There should be sufficient ventilation in the
enclosure to ensure that the meter's case is
always kept to less than 60C.
Meter Spacing.
Meters should be spaced apart sufficiently
to allow a free flow of ventilation air around
the meters, such that no part of the case will
exceed 60C
Side view of meter installed in panel
45mm +1mm -0mm
Gasket
Bracket screw (1 of 2)
92mm +1mm -0mm
Panel cutout
888888
Left side of meter case
U-Bracket
Slide the meter, with gasket
into the panel cutout
U-Bracket
Bracket screws
Front surface
of enclosure
Front surface
of meter
Gasket
Front surface
of enclosure
7