Theoretical Calibration - VETEC P1001/6-P Manual

Panel mounting process indicator / controller
Table of Contents

Advertisement

Theoretical Calibration - Low end calibration
This is when you type in the sensor's theoretical signal level at the top and bottom of
its range and the value to display, for each signal level.
If you have not done so before, please select Theoretical Calibration mode
from the Meter Calibration page.
This feature is available in Easy and Advanced Modes
Set1
1
Digit
Max/Min
Press 3 seconds
Set1
Digit
2
Max/Min
Display shows
dC A
followed by
on whether you have chosen current or
voltage input, then
Set1
3
Digit
Max/Min
Set1
Digit
Max/Min
4
5
Set1
Digit
Max/Min
You can set Zero first, if you prefer, but you will not be able to change the decimal
point position in the ZERO calibration step. This will not be an issue if your zero
calibration reading is 0, but may become confusing otherwise.
Set2
Output
Alarms
OK
Reset
Set2
Output
Alarms
OK
Reset
theor
dC V
or
, depending
In Lo
Set2
Output
Alarms
OK
Reset
Press to accept
Set2
Output
Alarms
OK
Reset
Set2
Output
Alarms
OK
Reset
Press to accept
Lockout Switch must be OFF
Circuit board
Press OK. You can now specify the
lowest input signal. Use DIGIT to
select each digit in turn, and the UP
or DOWN arrow to increase or
decrease each digit's value, as
required. eg set
04.0000
input is 4-20mA
Display now shows
can now specify the low reading.
Use DIGIT to select each digit in turn,
and the UP or DOWN arrow to increase
or decrease each digit's value, as re-
quired. eg set
000.000
range is 0 to 100.000
OFF
ON
if your
rd Lo
briefly. You
if your display
Done!