Direct Calibration - Full Scale Setting
This is when you connect the meter to your system and make the meter read what
you want it to, at 2 different points. This is the preferred calibration method, because
it allows you to calibrate the system as a whole.
How to do direct calibration:-
If you have not done so before, please select Direct Calibration mode from
the previous page.
First we recommend you set the FULL SCALE calibration ...
This feature is available in Easy and Advanced Modes
Set1
Digit
1
Press 3 seconds
Set1
2
Digit
Set1
3
Digit
Press for 3 seconds
Set1
4
Digit
5
Set1
Digit
18
Set2
Output
Alarms
OK
Max/Min
Reset
Set2
Output
Alarms
OK
Max/Min
Reset
Set2
Output
Alarms
OK
Max/Min
Reset
Set2
Output
Alarms
OK
Max/Min
Reset
Set2
Output
Alarms
OK
Max/Min
Reset
Press to accept
Lockout Switch must be OFF
Display shows
direCt
by
SEt Hi
Apply the highest calibration signal you
can achieve, ideally 100% of system
capacity. You can use less, but you will
get better accuracy with higher signals.
Press OK.
Press Set2 for 3 seconds. You can now
set your decimal point position using
the UP or DOWN buttons.
Press OK when done.
You can now set the display value you
want to see - use DIGIT to select each
digit in turn, and the UP or DOWN arrow
to increase or decrease each digit's
value, as required.
OFF
followed
Circuit board
ON
Done!