Offset adjustment

After you have calibrated your meter, you can use the
tions or subtractions to the reading, without affecting the calibration itself.
For example if your weighing structure is altered after calibration and you want to subtract
the effect of 37kg of extra metalwork which was welded to the hopper, you can easily do this
by entering a value of -37 in the offset value.
!! This feature is available in Advanced Mode only !!
Set1
Digit
1
Press 3 seconds
Set1
Digit
2
Set1
Digit
3
Set1
4
Digit
You may want to adjust a SCALE FACTOR value also, without affecting calibration. See
the separate SCALE page for this feature.
34
Set2
Output
Alarms
OK
Max/Min
Reset
Set2
Output
Alarms
OK
Max/Min
Reset
Set2
Output
Alarms
OK
Max/Min
Reset
Set2
Output
Alarms
OK
Max/Min
Reset
Press to accept
OFFSET
feature to make fine addi-
Lockout Switch must be OFF
Circuit board
Press repeatedly until you see
OFFSEt
, followed by the existing
offset value.
(Default is
Use DIGIT button to select each digit
in turn, UP or DOWN buttons to
increase or decrease each digit's
value. If you want to set a negative
value, use DIGIT to select the left
hand digit, and press the down button
to go below 0 to activate the - sign.
Press OK when done.
OFF
ON
000.000
)
Done!