Display Calibration Modes - VETEC P1001/6-P Manual

Panel mounting process indicator / controller
Table of Contents

Advertisement

You can choose from two main calibration methods.
1. Direct Calibration - this is when you connect the meter to your system and
make the meter read what you want it to, at 2 different points. This is the preferred
calibration method, because it allows you to calibrate the system as a whole.
2. Theoretical Calibration - this is when you type in the sensor's theoretical
signal level at the bottom and top of itsrange and then type in the value the
display should show, for each signal level.
How to choose a calibration method:-
This feature is available in Easy and Advanced Modes
Set1
Digit
1
Press 3 seconds
Set1
Digit
2
Press to select dirECt or thEor
Set1
Digit
3
If you chose Theoretical, you will now be asked whether your input signal
will be DC Current or DC voltage ... the display will show
by
dC A
Set1
Digit
4
Press to select dc A or dc V
Set1
Digit
5
Set2
Output
Alarms
OK
Max/Min
Reset
Set2
Output
Alarms
OK
Max/Min
Reset
Set2
Output
Alarms
OK
Max/Min
Reset
Press to accept
or
dC V
Set2
Output
Alarms
OK
Max/Min
Reset
Set2
Output
Alarms
OK
Max/Min
Reset
Press to accept
Meter Calibration Modes
Lockout Switch must be OFF
Display shows
CAL Src
dIreCt
or
thEor
(Default)
Display shows
Input
dC A
for current or
dC V
for voltage
(Default)
OFF
Circuit board
ON
then
Input
followed
then
Done!