Linearisation With Direct Calibration - VETEC P1001/6-P Manual

Panel mounting process indicator / controller
Table of Contents

Advertisement

Linearisation with Direct Calibration

If your system is non linear, you can calibrate the meter and correct for this with the
lineariser function.
You will need to apply a series of known loads, starting at 0 and working up to full scale. You
will then tell the meter what it should read for each applied load. You can use up to 10
points.
First, you must select Direct Calibration Mode (see page on calibration Modes)
Then, proceed as shown below...
This feature is available in Easy and Advanced Modes
Set1
Digit
1
Press together, briefly
Set1
Digit
2
Set1
Digit
3
Set1
Digit
4
Continued ...
20
Set2
Output
Alarms
OK
Max/Min
Reset
Set2
Output
Alarms
OK
Max/Min
Reset
Set2
Output
Alarms
OK
Max/Min
Reset
Set2
Output
Alarms
OK
Max/Min
Reset
Lockout Switch must be OFF
Display will show
Lin.On
Lin.OFF
(Default)
If the display shows
button briefly so that the display shows
Lin.On
, then press OK
The display will show
Ensure no load is applied to the system
and press OK.
The display will now show
You can now tell the meter what it should
display for this load.
Select each digit in turn with the DIGIT
button, and increase or decrease each
digit's value using the UP or DOWN
button, until the display is set as required.
Press OK when done.
The display will show
Press OK
OFF
or
Circuit board
ON
Lin.OFF
, press Set2
SEt 00
rd 00
Add.Pt