U U n n i i t t S S t t a a r r t t u u p p
Figure 53. Supply fan performance with variable frequency drive - 60 ton cooling only air-cooled - direct drive
plenum, 120% width
8.0
7.5
7.0
6.5
6.0
5.5
5.0
1600 RPM
4.5
1500 RPM
4.0
1400 RPM
3.5
1300 RPM
3.0
1200 RPM
2.5
1100 RPM
2.0
1000 RPM
1.5
1.0
0.5
0.0
0
2500
5000
I I m m p p o o r r t t a a n n t t : : Maximum static pressure leaving the
rooftop is 4.0" H
pressure drops from the supply fan to the
space cannot exceed 4.0" H
84
2000 RPM
1900 RPM
1800 RPM
1700 RPM
7500
10000
12500
15000
Airflow, CFM
O positive. The static
2
O.
2
2100 RPM
17500
20000
22500
N N o o t t e e s s : :
•
Shaded areas represent selectable area.
Contact your local Trane ® representative for
more information.
•
60 ton units with gas heat use the 30" DDP
fans. See
•
Supply fan performance curve includes
internal resistance of rooftop. For total static
pressure determination, system external
static must be added to appropriate
component static pressure drops
(evaporator coil, filters, optional economizer,
optional relief fan, optional heating system,
optional cooling only extended casing,
optional roof curb).
•
Maximum Cfm (for cULus approval) as
follows: 60 ton - 27,000 Cfm.
•
Minimum motor horsepower is 10 hp (2 x 5
hp motors). Maximum motor horsepower is
40 hp (2 x 20 hp motors). Maximum fan RPM
is 2,100.
25000
27500
30000
Figure 59, p. 90
.
RT-SVX072A-EN