Table 71. Relief/return fan VFD parameters
Menu
ID
0-01
0-03
Operation
Display
0-06
0-40
1-20
1-22
1-23
1-24
Load and Motor
1-25
1-73
1-90
2-00
Brakes
2-01
2-04
3-02
3-03
3-15
Reference /
3-16
Ramps
3-17
3-41
3-42
4-10
4-12
Limits /
4-14
Warnings
4-18
4-19
148
Description
Parameter Setting
Language
[0] English US
Regional Settings
[1] North American
Set to applicable unit power supply
[102] 200-240V/60Hz for 208 & 230V/60Hz units
[122] 440-480V/60Hz for 460V/60Hz units
Grid Type
[132] 525-600V/60Hz for 575V/60Hz units
[12] 380-440v/50Hz for 380 & 415V/50Hz supply
For IT Grid (no ground connections) or Corner grounded Delta power supply systems,
the applicable voltage/Hz and IT-Grid or Delta should be selected.
[Hand on] - Key on
[0] Disabled
LCP
Motor Power (KW/HP)
Per Motor Nameplate HP - KW
Motor Voltage (V)
Per Motor Nameplate Voltage
Motor Frequency (HZ)
Per Motor Nameplate Frequency
Motor Current (A)
Per Motor Nameplate FLA
Motor Nominal Speed
Per Motor Nameplate Rated Speed
(RPM)
Flying Start
[1] Enabled
Motor Thermal
[4] ETR Trip1
Protection
DC Hold / Preheat
[0] 0%
Current (%)
DC Brake Current (%)
[0] 0%
DC Brake Cut In
[10] 10 Hz
Speed
Minimum Reference
[22] 22 Hz
(HZ)
Maximum Reference
[60] 60 Hz
(HZ)
[11] Local bus reference
Reference 1 Source
[0] No function
Reference 2 Source
[0] No function
Reference 3 Source
Ramp 1 Ramp up
[30] 30s
Time (S)
Ramp 1 Ramp down
[30] 30s
Time (S)
Motor Speed Direction
[0] Clockwise
Motor Speed Low
[22] 22 Hz
Limit [HZ]
Motor Speed High
[60] 60 Hz
Limit (Hz)
Current Limit (%)
[100] 100%
Max Output
[60] 60 Hz
Frequency (Hz)