1700 Rpm - Trane IntelliPak 1 Installation, Operation And Maintenance Manual

Commercial packaged rooftop air conditioners with vav or szvav controls and eflex/ edrive
Table of Contents

Advertisement

U U n n i i t t S S t t a a r r t t u u p p
N N o o t t e e s s : :
Fan performance for 20 and 25 tons rooftops
is identical. Contact your local Trane ®
representative for information on oversized
motors.
Shaded areas represent selectable area.
Contact your local Trane ® representative for
more information.
Supply fan performance curve includes
internal resistance of rooftop. For total static
pressure determination, system external
static must be added to appropriate
Figure 40. Supply fan performance with variable frequency drive - 20 and 25 tons cooling only - direct drive plenum,
80% width
8.0
7.5
2200 RPM
7.0
2100 RPM
6.5
2000 RPM
6.0
5.5
1900 RPM
5.0
1800 RPM
4.5

1700 RPM

4.0
1600 RPM
3.5
1500 RPM
3.0
1400 RPM
1300 RPM
2.5
1200 RPM
2.0
1100 RPM
1.5
1000 RPM
1.0
0.5
0.0
0
1000
2000
I I m m p p o o r r t t a a n n t t : : Maximum static pressure leaving the
rooftop is 4.0" H
pressure drops from the supply fan to the
space cannot exceed 4.0" H
70
2300 RPM
2400 RPM
3000
4000
5000
6000
Airflow, CFM
O positive. The static
2
O.
2
component static pressure drops
(evaporator coil, filters, optional economizer,
optional relief fan, optional heating system,
optional cooling only extended casing,
optional roof curb).
Maximum Cfm (for cULus approval) as
follows: 20 ton - 9,000 Cfm, 25 ton - 11,000
Cfm.
Minimum motor horsepower is 3 hp.
Maximum motor horsepower is 20 hp.
Maximum fan RPM is 1750.
7000
8000
9000
10000
11000
12000
RT-SVX072A-EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Symbio 800

Table of Contents