Summary Of Connections - First Alert FA162C Installation Instructions Manual

2-partitioned
Hide thumbs Also See for FA162C:
Table of Contents

Advertisement

GEL LEAD ACID TYPE.
FOR REPLACEMENT,
3A
BATTERY NORMALLY NEED NOT BE
USE SAME VALUE
REPLACED FOR AT LEAST 3 YRS.
(e.g. ADEMCO No. 90-12)
BATTERY CAPACITY FOR EMERGENCY
STANDBY USE AT LEAST 4 HOURS.
BLACK
CHARGING
BATTERY
VOLTAGE
+
RED
12V, 4AH
13.8VDC
+
TO DETERMINE TOTAL STANDBY
LOAD ON BATTERY, ADD 100mA TO
TOTAL OF AUX. POWER OUTPUT AND
CONNECTOR
REMOTE KEYPAD CURRENTS.
TABS
USE UL LISTED
LIMITED ENERGY
1
2
3
CABLE FOR ALL
CONNECTIONS
PLUG-IN TRANSFORMER
16.5VAC, 25VA (e.g. ADEMCO
No. 1321)
TO 110VAC
UNSWITCHED
OUTLET (24HR)
USE 4300 TRANSFORMER INTERFACE IN
PLACE OF 1321 WHEN POWER LINE CAR-
RIER DEVICES ARE BEING USED (SEE
INSTRUCTIONS FOR CONNECTIONS)
+
ALARM OUTPUT
10.5-13.8VDC, 2A MAX. (700mA MAX. FOR UL
USAGE, INCLUDING AUX POWER)
STEADY FOR BURGLARY/PANIC, TEMPORAL PULSE
SOUNDING FOR FIRE (e.g. USE ADEMCO No. 702
SIREN, OR 12V BELL). SEE INSTRUCTIONS.
BATTERY FUSE
REMOTE
KEYPAD
9-PIN CONNECTOR
PARTITION 2
USED FOR 4300
TRANSFORMER
CONNECTIONS (FOR
OPTIONAL POWER LINE
CONNECTOR
CARRIER DEVICES)
FOR PARTITION
SEE INSTRUCTIONS.
2 KEYPAD(S)
1 2 3 4 5 6 7 8 9
USE 4142TR CABLE
TO TERM 4
TO TERM 5
TO TERM 6
TO TERM 7
4
5
6
7
8
9
+
AUX. POWER
SMOKE
OUTPUT
10.5-13.8VDC
600mA MAX.
INTERRUPTS
FOR FIRE
ALARM RESET
NOTE:
KEYPAD(S)
CURRENT (IN
BOTH
PARTITIONS)
AND ALL
OTHER
DEVICES
2000
DRAWING
OHMS
REMOTE
POWER FROM
EOLR
KEYPAD
TERMS 4 & 5
PARTITION 1
MUST BE
INCLUDED IN
REMOTE KEYPADS
AUX CURRENT
TRANSMITTER MODULE (20mA)
EACH PARTITION CAN
DRAIN
USE:
CALCULATIONS
Wireless Bi-directional Keypad)
FA210KP (30mA)
FA250KP (40mA)
FA4285 VOICE MODULE (160mA)
FA450KP (70mA)
FA550KP (70mA)
No. 7720 PLUS OR 7820
LOCAL PROGRAMMING
MUST BE DONE WITH
MAY ALSO BE CONNECTED.
AN FA550KP CONNECT-
ED TO PARTITION 1,
ACCOMPANYING THOSE DEVICES.
BUT NEED NOT REMAIN
IN THE SYSTEM.
ADEMCO No. 4219
WIRED EXPANSION MODULE
(8 ADD'L EOLR WIRED ZONES)
-OR-
ADEMCO No. 4229
WIRED EXPANSION/RELAY MODULE
(8 ADD'L EOLR WIRED ZONES PLUS 2
BLK
OUTPUT RELAYS)
RED
-OR-
GRN
ADEMCO No. 4204 RELAY MODULE
(4 OUTPUT RELAYS)
YEL
AND/OR
ADEMCO 5881 Type
RF RECEIVER
BLK
BLK
WIRELESS ZONES
RED
RED
5881L:
UP TO 8
GRN
GRN
5881M:
UP TO 16
YEL
5881H:
UP TO 30
YEL
10
11
12
13
14
15
16
2000
2000
2000
2000
OHMS
OHMS
OHMS
OHMS
EOLR
EOLR
EOLR
EOLR
• MAXIMUM LOOP RESISTANCE (EACH ZONE) 300 OHMS
OPTIONAL:
(PLUS EOLR)
No. 5800TM
• RESPONSE, ZONES 1-8: 10, 350, OR 700 MSEC
(PROGRAMMABLE)
(for No. 5827BD
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES.
OPERATION IS SUBJECT TO THE FOLLOWING TWO CON-
AND/OR
DITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL
INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT
AND/OR
ANY INTERFERENCE THAT MAY CAUSE UNDESIRED
OPERATION.
LONG RANGE RADIO
COMPLIES WITH FCC RULES, PART 68
SEE INSTRUCTIONS
FCC REGISTRATION NO. AC398U-68192-AL-E
RINGER EQUIVALENCE: 0.7B.
FOR COMPLETE INFORMATION, SEE INSTRUCTIONS N7526-1V3
SET UNIT'S DIP
SWITCH FOR
DEVICE
AUX PWR
+
5
ADDRESS
OUTPUT
-
TERMS
OF "1".
4
SEE
INSTRUCTIONS.
4-WIRE SMOKE
OR COMBUSTION
DETECTOR
SET RECEIVER'S
TO HI SIDE OF SELECTED ZONE
DIP SWITCH
+
FOR DEVICE
HEAT
ZONES 2–7
*
ADDRESS OF
DETECTOR
"0". SEE
-
INSTRUCTIONS.
TO LO SIDE OF SELECTED ZONE
*
IF PROGRAMMED FOR FIRE
17
18
19
20
21
22
TIP
RING
(BROWN)
(GRAY)
(GREEN)
HANDSET
TELEPHONE WIRING
(VIA RJ31X JACK AND DIRECT
CONNECT CORD.
FOR CONNECTION OF
OPTIONAL FA4285 VOICE MOD-
ULE TO PHONE TERMINALS, SEE
INSTRUCTIONS.
WARNING:
TO PREVENT RISK OF SHOCK,
DISCONNECT TELEPHONE LINE AT
TELCO JACK BEFORE SERVICING
2000
2000
2000
THIS UNIT.
OHMS
OHMS
OHMS
EOLR
EOLR
EOLR
THIS EQUIPMENT SHOULD BE INSTALLED IN
ACCORDANCE WITH THE NATIONAL FIRE
PROTECTION ASSOCIATION'S STANDARD 74
(NATIONAL FIRE PROTECTION ASSOC.,
BATTERYMARCH PARK, QUINCY, MA 02269).
PRINTED INFORMATION DESCRIBING
PROPER INSTALLATION, OPERATION,
TESTING, MAINTENANCE, EVACUATION
PLANNING AND REPAIR SERVICE IS TO BE
PROVIDED WITH THIS EQUIPMENT.
WEEKLY TESTING IS REQUIRED TO ENSURE
PROPER OPERATION OF THIS SYSTEM.
+
RED
BLK
EOL
POWER
+
SUPER-
-
VISION
VIOLET
RELAY
MODULE
A77-716B
2000
OHMS
EOLR
23
24
25
TIP
RING
(RED)
INCOMING
PHONE LINE
EARTH
GROUND
SEE INSTRUCTIONS
FOR PROPER
GROUNDING

Advertisement