Installation prerequisites for standards

The GP2000-VM41 is a UL/c-UL listed product. (UL file No.E182139)
This unit conforms as a product to the following standards:
UL508 Industrial Control Equipment
ANSI/ISA 12.12.01 Nonincendive Electrical equipment for Use in Class I Divi-
sion 2 Hazardous (Classified) Locations.
CAN/CSA-C22.2 No. 142 Process Control Equipment
CAN/CSA-C22.2 No. 213 Non-Incendive Electrical Equipment for Use in Class
I, Division 2 Hazardous Locations.
GP2000-VM41 (UL Registration Model: 2980020-01)
<Cautions>
• The VM must be used as a built-in component of a GP/GLC unit.
• If this unit is installed so as to cool itself naturally, be sure to attach the VM to a GP/
GLC unit that is installed in a vertical panel. Also, be sure that the GP/GLC unit is
mounted at least 100 mm away from any adjacent structures or equipment. If these
requirements are not met, the heat generated by the GP/GLC unit's internal compo-
nents or the VM Unit may cause the combination to fail to meet UL/c-UL standard
requirements.
Hazardous Locations - Comploance and Handing Cautions:
1. Power, input and output (I/O) wiring must be in accordance with Class I, Division 2
wiring methods - Article 501- 10(B) of the National Electrical Code, NFPA 70
within the United States, and in accordance with Section 18-152 of the Canadian
Electrical Code for units installed within Canada.
2. Suitable for use in Class I, Division 2, Groups A, B, C and D, Hazardous Locations.
3. WARNING: Explosion hazard - substitution of any components may impair suit-
ability for Class I, Division 2.
4. WARNING: Explosion hazard - when in hazardous locations, turn power OFF
before replacing or wiring modules.
5. WARNING: Explosion hazard - do not disconnect equipment unless power has
been switched OFF, or the area is known to be non-hazardous.
The GP2000-VM41 is a CE marked product that conforms to EMC directives
EN55011 class A and EN61000-6-2.
This marking requires the attachment of a Ferrite Core (included) to each video
cable used.