Monitor Menu - Tekmar tekmarNet 2 House Control 406 Installation & Operation Manual

Table of Contents

Advertisement

Adjust Menu (6 of 6)
Item Field
Default = 90°F (32°C)
If DHW MODE = 5
Access: Installer
Set to:
Access: Installer
Set to:
(15.5 to 93.5°C)
Access: Installer
Set to:
Access: User
Set to:
Monitor Menu (1 of 2)
The Monitor menu items provide information about the system's operation and performance. To clear any item back to
default, press and hold the Up and Down buttons while viewing that item.
Item Field
Access: User
Access: User
Access: User
Access: User
Access: User
Range
70 to 180°F
(21 to 82°C)
Default = 125°F
DHW OCCUPIED
(51.5°C) If DHW
Selects the temperature of the indirect DHW tank when DHW MODE = 1-4.
MODE = 1-4
Selects the temperature of the DHW pre-heat tank when DHW MODE = 5.
Note: Item is only available when a DHW sensor is installed and the DHW
Mode is set to 1 to 5.
DHW UNOCCUPIED
ON, OFF
Selects whether or not the indirect DHW tank should be heated to during
Default = ON
Unoccupied time periods.
Note: Item is only available when a DHW sensor is installed, the DHW Mode is set
to 1 to 5 and a schedule is available or a User Switch is present on the system.
60 to 200°F
Default = 180°F
SETPOINT
(82°C)
Boiler target to satisfy a setpoint demand.
°F or °C
Default = °F
UNITS
Selects units for temperature display.
Range
-76 to 149°F
OUTDOOR LOW
(-60.0 to 65.0°C)
Records the lowest outdoor temperature since the item was last reset. Press
and hold the Up and Down buttons while viewing to reset.
-76 to 149°F
OUTDOOR HIGH
(-60.0 to 65.0°C)
Records the highest outdoor temperature since the item was last reset. Press
and hold the Up and Down buttons while viewing to reset.
0 to 9999 Hours
RUN TIME (HEAT PUMP STAGE 1)
Default = 0 hr
The total 'on' time of the Y1 relay since the item was last reset. Press and hold
the Up and Down buttons while viewing to reset.
RUN TIME (HEAT PUMP STAGE 2)
0 to 9999 Hours
The total 'on' time of the Y2 relay since this item was last reset. Press and hold
Default = 0 hr
the Up and Down buttons while viewing to reset.
Note: Item is only available when HP TYPE = 2STG or ROT.
RUN TIME (BOILER)
0 to 9999 Hours
The total 'on' time of the backup relay since the item was last reset. Press and
Default = 0 hr
hold the Up and Down buttons while viewing to reset.
Note: Item is only available when WATERTEMP = T + B or T+MB.
Description
Description
29 of 48
SECTION F
SECTION F
SECTION H
© 2011
D 406 - 12/11

Advertisement

Table of Contents
loading

Table of Contents