Monitor Menu (2 of 2)
Item Field
Access: Installer
Aux
Access: Installer
Xfr
Access: Installer
Var
Access: Installer
Access: Installer
Access: Installer
Access: Installer
Access: Installer
Access: Installer
Access: Installer
Access: Installer
© 2011
D 406 - 12/11
Range
RUN TIME (AUXILIARY)
0 to 9999 Hours
The total 'on' time of the Backup relay since the item was last reset. Press and
Default = 0 hr
hold the Up and Down buttons while viewing to reset.
Note: Item is only available when BACKUP = AUX.
RUN TIME (TRANSFER PUMP)
0 to 9999 Hours
The total running time of the Transfer Pump since the item was last reset. Press
Default = 0 hr
and hold the Up and Down buttons while viewing to reset.
Note: Item is only available when BACKUP = XFER
RUN TIME (VARIABLE SPEED PUMP)
0 to 9999 Hours
The total running time of the Variable Speed Pump since the item was last reset.
Default = 0 hr
Press and hold the Up and Down buttons while viewing to reset.
Note: Item is only available when BACKUP = VAR.
0 to 9999 Hours
RUN TIME (HP LOOP PUMP)
Default = 0 hr
The total running time of the HP Loop Pump since the item was last reset. Press
and hold the Up and Down buttons while viewing to reset.
0 to 9999 Hours
RUN TIME (TANK PUMP)
Default = 0 hr
The total running time of the Tank System Pump since this item was last reset.
Press and hold the Up and Down buttons while viewing to reset.
RUN TIME (MIX SYSTEM PUMP)
0 to 9999 Hours
The total running time of the Mix System Pump since this item was last reset.
Default = 0 hr
Press and hold the Up and Down buttons while viewing to reset.
Note: Item is only available when WATERTEMP = T + M or T + MB.
RUN TIME (BOIL SYSTEM PUMP)
0 to 9999 Hours
The total running time of the Boil System Pump since this item was last reset.
Default = 0 hr
Press and hold the Up and Down buttons while viewing to reset.
Note: Item is only available when WATERTEMP = T + B or T + MB.
RUN TIME (DHW PUMP)
0 to 9999 Hours
The total running time of the DHW Pump since this item was last reset. Press
Default = 0 hr
and hold the Up and Down buttons while viewing to reset.
Note: Item is only available when DHW MODE ≠ OFF.
DEW POINT MIX
– – –, -35 to 273°F
Highest dewpoint of all humidity sensors on the mix loop.
(-37 to 134°C)
Note: Item is only available when WATERTEMP = T + M or T + MB and a
humidity sensor has been detected on the mix bus.
DEW POINT TANK
– – –, -35 to 273°F
Highest dewpoint of all humidity sensors on the tank loop.
(-37 to 134°C)
Note: Item is only available when a humidity sensor has been detected on
the tank bus.
DEW POINT BOIL
– – –, -35 to 273°F
Highest dewpoint of all humidity sensors on the boiler loop.
(-37 to 134°C)
Note: Item is only available when WATERTEMP = T + B or T + MB and a
humidity sensor has been detected on the boiler bus.
Description
30 of 48