Front Low Voltage Wiring Diagram --------------------------- ----------------------------------- ------ -
Mix Supply / DHW
Universal Sensor
Tank Supply
Universal Sensor
Boiler Supply
Universal Sensor
HP Return
Universal Sensor
Outdoor Sensor
Setpoint Call
DHW Call
from DHW
Tank Aquastat
(optional)
Low Voltage Wiring - - - ------------------ ------------------------------------------------------- --- --- -- -
----------------------------------- --------------------------------------------------
External Power Supply
It is strongly recommended that a transformer with an in-line
fuse be used in order to protect the transformer from high
currents. The tekmar Transformer 009 includes a fuse.
Connect the 24 V (ac) leads from the transformer to the C
and R terminals marked "Input Power" on the 406.
tekmarNet
®
2 Thermostats (tN2)
The 406 is designed to operate with tekmarNet
They provide the heating and cooling control for each zone,
and communicate with any other tekmarNet
system.
Connect the tN2 terminals from each thermostat to the cor-
responding tN2 terminals for each zone on the 406.
Zone Valves
Wire the zone valves to the C and Vlv terminals on the 406.
End switches on zone valves are not required when using
the 406.
tN4 Expansion Terminals
The 406 uses the Expansion tN4 and C terminals to com-
municate with additional thermostats, setpoint controls, and
®
other tekmarNet
devices. Connect to either the Tank or the
Boil / Mix tN4 and C terminals on the 406.
© 2011
D 406 - 12/11
---------------------------------------------------------------------
tekmarNet
®
2 Thermostats
tN2 tN2
tN2 tN2
tN2 tN2
Mix/DHW
tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2 Rc1 Y1 O/B
No Power
Zone 1
Zone 2
Zone 3
Menu
Item
House Control 406
Zone 1
Zone 2
Zone 3
Zone 4
Input Power
C
Vlv
C
Vlv
C
Vlv
C
Vlv
24 V (ac) Zone Valves
Tank
To add additional Tank water temperature zones to the system,
install a tekmarNet
Connect the Tank terminals, tN4 and C, on the 406 to the
corresponding tN4 and C Expansion terminals on the ex-
ternal Wiring Center.
Boil / Mix
To add additional Boil or Mix water temperature zones to the
®
2 Thermostats.
system, install a tekmarNet
Connect the Boil/Mix terminals, tN4 and C, on the 406 to
®
device on the
the corresponding tN4 and C Expansion terminals on the
external Wiring Center.
Domestic Hot Water (DHW) or Setpoint Call
When the control receives a DHW Call or Setpoint Call for heat
it will override Outdoor Reset and Indoor Feedback and operate
the boiler to heat the DHW tank or the Setpoint equipment.
To create a DHW call, wire a dry contact switch to the DHW
call terminals.
To create a Setpoint call, wire a dry contact switch to the
Setpoint call terminals.
6 of 48
tN2 tN2
Zone 4
C
R
R
C
24 V (ac) Transformer 009
®
Wiring Center.
®
Wiring Center.
®
tekmarNet
4 Expansion to
Wiring Centers, Timers, or
User Switch
tN4 Tank
Expansion
tN4 Boil/Mix
Expansion
Modulating
Boiler
1
One Stage
Boiler T-T
One or Two Stage
Heat Pump
L
N