Toolbox Menu (1 of 1)
The Toolbox Menu is a location for system information and Test functions. If any errors are present on the system,
they will be located at the beginning of this menu.
Item Field
Access: Installer
Access: Installer
Access: User
Access: User
Access: Installer
Access: Installer
Access: Installer
Access: Installer
Access: Installer
See Troubleshooting
Access: Installer
Range
USER TEST
ON or OFF
Begins the test routine which tests the main control's functions. See the Testing
Default = OFF
the Control section for more details. Use the up button to turn the User Test
On.
MAX HEAT
ON or OFF
When selected, control operates the system up to maximum set temperatures.
Default = OFF
Will operate up to 24 hours, or can be manually turned Off. See the Max Heat
section for more details.
Flashes Between
TYPE AND SOFTWARE VERSION
J12 & ##A - ##Z
Displays the type number of the product, followed by the current software
version beneath.
ACCESS LEVEL
INST (Installer)
Selects the access level of the control, which determines the Menu items
or USER
available. USER provides the most limited level of access and shows the fewest
Default = INST
possible items.
When set to USER, all thermostats are locked and the number of thermostat
settings available are reduced.
OFF, SEL
FACTORY DEFAULTS
Default = Off
Loads the factory default settings. Hold the Up and Down buttons for 1 second
until SEL is shown.
ZONE 1-4 DEVICES
0 to 4 devices
Displays the number of tN2 thermostats connected to the House Control on zones
1-4. These thermostats could be assigned to be on the Tank, Mix or Boil bus.
TANK DEVICES
0 to 24 devices
Displays the number of devices connected to the Tank bus expansion terminals,
tN4 and C.
MIX DEVICES
0 to 24 devices
Displays the number of devices connected to the Mix bus expansion terminals,
tN4 and C.
Note: Item is only available when the Mix bus is enabled.
BOIL DEVICES
0 to 24 devices
Displays the number of devices connected to the Boil bus expansion terminals,
tN4 and C.
Note: Item is only available when the Boil bus is enabled.
HISTORY 1-5
Displays a history of any past errors that have occurred on the system. Will clear
Guide
after 30 days, or press Up and Down buttons for 1 second to manually clear.
The last 5 history items will display if present.
Description