00.001 {01.007}
RW
Num
OL
±VM_NEGATIVE_REF_CLAMP1 Hz
RFC-A
Set Pr 00.001 at the required minimum output frequency of the drive for both directions of rotation.
The drive speed reference is scaled between Pr 00.001 and Pr 00.002. Pr 00.001 is a nominal value;
slip compensation may cause the actual frequency to be higher. When the drive is jogging, Pr 00.001
has no effect.
00.002 {01.006}
RW
Num
OL
±VM_POSITIVE_REF_CLAMP Hz
RFC-A
Set Pr 00.002 at the required maximum output frequency for both directions of rotation. The drive
speed reference is scaled between Pr 00.001 and Pr 00.002. Pr 00.002 is a nominal value; slip
compensation may cause the actual frequency to be higher. The drive has additional over-speed
protection.
00.003 {02.011}
RW
Num
OL
±VM_ACCEL_RATE s/100 Hz
RFC-A
Set Pr 00.003 at the required rate of acceleration. Note that larger values produce lower
acceleration. The rate applies in both directions of rotation.
32
Number
Bit
Num
Bit
parameter
parameter
Protected
Rating
PT
RA
parameter
dependent
Minimum Reference Clamp
Maximum Reference Clamp
Acceleration Rate 1
Binary
Txt
Text string
Bin
parameter
Power-down
US
User save
PS
save
0.00 Hz
50.0 Hz default: 50.00 Hz
60.0 Hz default: 60.00 Hz
5.0 s/100 Hz
Unidrive M200-201 Quick Start Guide
FI
Filtered
DE Destination
US
US
US
Issue Number: 6