Diagnostics - Emerson M200-01200024A10101AB100 Quick Start Manual

Frame sizes 1 to 4
Table of Contents

Advertisement

8

Diagnostics

Users must not attempt to repair a drive if it is faulty, nor carry out fault diagnosis other
than through the use of the diagnostic features described in this chapter.
If a drive is faulty, it must be returned to the supplier of the drive for repair.
WARNING
Table 8-1 Trip indications
Trip
Condition
code
C.Acc
NV Media Card Write fail
The Menu 0 parameter
C.bt
modification cannot be saved to
the NV Media Card
NV Media Card cannot be
C.by
accessed as it is being accessed
by an option module
NV Media Card file/data is different
C.cPr
to the one in the drive
NV Media Card data location
C.d.E
already contains data
C.dAt
NV Media Card data not found
NV Media Card data structure
C.Err
error
C.FuL
NV Media Card full
NV Media Card trip; option
modules installed are different
C.OPt
between source drive and
destination drive
NV Media Card data blocks are not
C.Pr
compatible with the drive derivative
NV Media Card has the Read Only
C.rdo
bit set
NV Media Card Trip; The voltage
C.rtg
and / or current rating of the source
and destination drives are different
NV Media Card trip; Option module
C.SI
file transfer has failed
NV Media Card parameter set not
C.tyP
compatible with current drive mode
cL.A1
Analog input 1 current loss
CL.bt
Trip initiated from the Control Word
Cur.c
Current calibration range
Cur.O
Current feedback offset error
Drive parameters are being
d.Ch
changed
dEr.E
Derivative file error
dEr.I
Derivative product image error
Unidrive M200-201 Quick Start Guide
Issue Number: 6
Description
Unable to access the NV Media Card.
The necessary boot file has not been created on the NV media
card fitted to the drive to take the new parameter value. This
occurs when Parameter Cloning (00.030) is changed to auto or
boot mode, but the drive is not subsequently reset.
An attempt has been made to access a file on NV Media Card,
but the NV Media Card is already being accessed by an option
module. No data is transferred.
A C.cPr trip is initiated if the parameters on the NV Media Card
are different to the drive.
Attempt has been made to store data on a NV Media Card in a
data block which already contains data.
Attempt has been made to access non-existent file or block on
the NV Media Card.
Attempt has been made to access the NV Media Card but an
error has been detected in the data structure on the card.
Resetting the trip will cause the drive to erase and create the
correct folder structure.
There is not enough space left on the card.
The parameter data or default difference data is being
transferred from the NV Media Card to the drive, but the option
module category is different between the source and destination
drives.
If Drive Derivative is different between the source and target
drives. Refer to Drive User Guide.
Attempt has been made to modify a read-only NV Media Card or
a read-only data block.
The current and / or voltage ratings are different between source
and destination drives.
The C.Sl trip is initiated, if the transfer of an option module file to
or from a module failed because the option module does not
respond correctly.
The drive mode in the data block on the NV Media Card is
different from the current drive mode.
Current loss was detected in current mode on Analog input 1
(Terminal 2).
Initiated by setting bit 12 on the control word when the control
word is enabled. Refer to Drive User Guide
Current calibration range error.
Current offset is too large to be trimmed.
A user action or a file system write is active that is changing the
drive parameters and the drive has been commanded to enable.
Contact the supplier of the drive.
Contact the supplier of the drive