Installation - Veris Industries H8150-1600-4-3 Installation Manual

Energy meter
Table of Contents

Advertisement

Installation Guide
Power Monitoring
H81xx

Installation

Z205338-0F
Page 5 of 10
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
1.888.610.7664
Disconnect and lock out all power sources during installation and configuration.
If making connections to the meter through more than one metallic conduit, use a bonding
plate (Veris part number AH11 or equivalent) to prevent electric shock.
1. Verify that the serial number on the meter matches the serial numbers on the current transformers (CTs). These are calibrated
as a set, and mixing transformers with non-matching meters may damage the device when power is applied. The meter's serial
number is printed on the label affixed to the inside of the front cover, and the CT serial number is on the CT label. If using 100 A
CTs, serial number matching does not apply.
Match serial numbers
between meters and CTs.
Serial number matching does
not apply if using 100 A CTs.
2. Mount the meter.
3. Attach the CTs to the conductors. Local code requirements may require a mounting bracket. For maximum accuracy, run the
conductor through the center of the current transformer window.
4. Optional step, per NEC and local regulations: Attach external fuses (not included with the H81xx devices). Verify that the fuse
rating is adequate for the applied voltage, with a current rating of ½ Amp (T) slow blow. Select fuses with a fault current rating
that matches the power source rating.
Use fuses compatible with this meter:
Single phase
Veris AH02
Two phase
Veris AH03
Installer Supplied Fuses
Three phase
Veris AH04
©2013 Veris Industrie
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
www.calcert.com
15
10
20
5
25
0
30
Accessory bonding
plate or equivalent
required when more
than one metallic
conduit will be used.
1/2A (T) SLO-BLO
ØA
ØB
ØC
N
Shock Hazard!
VERIS INDUSTRIES
1-800-354-8556
Bond multiple
metallic conduit
runs with available
bonding plate
(Veris AH11 or equivalent)
sales@calcert.com