Installation - Veris Industries H81 Series Installation Manual

Hide thumbs Also See for H81 Series:
Table of Contents

Advertisement

installation

Disconnect and lock out all power sources during
installation and configuration.
If making connections to the meter through more than
one metallic conduit, use a bonding plate (Veris part
number AH11 or equivalent) to prevent electric shock.
1.
Verify that the serial number on the meter matches the serial numbers on the
current transformers. These are calibrated as a set, and mixing transformers with
non-matching meters may damage the device when power is applied. The meter's
serial number is printed on the label affixed to the inside of the front cover, and
the current transformer serial number is on the transformer label.
2.
Mount the meter.
3.
Attach current transformers to conductors. Local code requirements may require a
mounting bracket. For maximum accuracy, run the conductor through the center
of the current transformer window.
4.
Optional step, per NEC and local regulations:
with the H81xx devices; installer must provide). Verify that fuse rating is adequate
for the applied voltage, with a current rating of 1/2 Amp (T) SLO-BLO. Select fuses
with a fault current rating that matches the power source rating.
Z205338-0C
PAGE 6
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Attach external fuses (not included
1/2A (T) SLO-BLO
ØA
ØB
ØC
N
Installer Supplied Fuses
Use fuses compatible with this meter:
Single phase
Veris AH02
Two phase
Veris AH03
Three phase
Veris AH04
©2009 Veris Industries USA 800.354.8556 or +1(0)503.598.4564 / support@veris.com
H81xx
Serial numbers are printed
on labels on the inside of the
meter cover and on the side
of the current transformer.
Only connect transformers
and meters with matching
serial numbers.
Accessory bonding
plate or equivalent
required when more
than one metallic
conduit will be used.
Bond multiple
metallic conduit
runs with available
bonding plate
or equivalent
(see Veris part AH11)
INSTALLATION GUIDE
Shock Hazard!
VERIS INDUSTRIES
1-800-354-8556