Veris Industries Hawkeye 8025 Installation Instructions Manual

Veris Industries Hawkeye 8025 Installation Instructions Manual

Networked (n2 bus) power meter

Advertisement

Quick Links

Applications
 Tenant submetering
 Energy management & performance contracting
 Departmental costing in manufacturing facilities
 Cooling plant optimization
Easy cost-effective installation
 Precision transducer electronics and high accuracy instrument grade CT's in a
single easy to install package...reduces the number of installed components
 Unique split-core design eliminates the need to remove conductors
 Reduced wiring costs...up to 63 meters on a single drop, address range 1 to 63
 Fits easily into distribution panels...lowest total installed cost
 Automatically detects phase reversal...eliminates the need to be concerned
with CT load orientation
High Accuracy
 ± 1% accuracy conforms to ANSI C12.1 metering standards
NOTE: This equipment has been tested by the manufacturer and found to
comply with the limits for a class A digital device, pursuant to part 15 of the
FCC Rules. These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial envi-
ronment. This equipment generates, uses, and can radiate radio frequency
energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation
of this equipment in a residential area is likely to cause harmful interference
in which case the user will be required to correct the interference at his own
expense. Modifications to this product without the express authorization of
Veris Industries nullify this statement.
P/N Z101640-0C
The
VERIS INDUSTRIES
solution for
local or remote
electrical metering
and submetering
in commercial
buildings!
http://www.veris.com
OPERATION
The H8025 and H8026, three-phase power transducers monitor energy
parameters from Aggregate kW (real power) and kWH (consumption) to power
factor per phase. With™ two platforms to choose from (H8025 Energy only
or H8026 Enhanced data stream) the applications for the H-8000 Series are
diverse; such as, aggregate billing, tenant submetering, energy management,
performance contracting, demand limiting and cooling plant optimization.
• This product is not intended for life or safety applications. This prod-
uct is not intended for installation in hazardous or classified locations.
• Potential electrocution hazard exists. Installing sensors in an energized
motor control center or on any energized conductor can be hazardous.
• Read instructions thoroughly prior to install
Severe injury or death can result from electrical shock during contact with
high voltage conductors or related equipment. Disconnect and lock-out
all power sources during installation and service. Applications shown are
suggested means of installing sensors, but it is the responsibility of the
installer to ensure that the installation is in compliance with all national
and local codes. Installation should be attempted only by individuals
familiar with codes, standards, and proper safety procedures for high-volt-
age installations.
Installation Instructions
Hawkeye 8025/8026
Networked (N2 Bus) Power Meter
Compatible with Johnson Controls, Inc.
Metasys® & Companion® Systems
PORTLAND, OREGON USA
(503) 598-4564 FAX (503) 598-4664
1-800-354-8556
email:sales@veris.com
WARNING--REFER SERVICING TO
QUALIFIED PERSONNEL ONLY!
®

Advertisement

Table of Contents
loading

Summary of Contents for Veris Industries Hawkeye 8025

  • Page 1 Modifications to this product without the express authorization of installer to ensure that the installation is in compliance with all national Veris Industries nullify this statement. and local codes. Installation should be attempted only by individuals familiar with codes, standards, and proper safety procedures for high-volt- age installations.
  • Page 2: Product Diagram

    PRODUCT DIAGRAM VOLTAGE LEADS Connect the leads to the three-phase source to be monitored. Input range is 208 to 480V. MANDATORY FUSE PER NEC Maximum current draw is 60 mA. Fuses provided by factory are rated 1/2A., 600V, 200kAIC. For continued protection, replace only with same type and rating.
  • Page 3: Installation - Wiring Diagram

    INSTALLATION - WIRING DIAGRAM TYPICAL 208/480 VAC 3Ø, 3,4 WIRE INSTALLATION N2 BUS When monitoring devices controlled by variable frequency drives, always connect the meter(s) to the line side (NEVER the load side). CONNECTING H8000 SERIES METERS TO THE LOAD SIDE OF A VARIABLE FREQUENCY DRIVE WILL PERMANENTLY DAMAGE THE ELECTRONICS! Note: The meter cannot communicate on the N2 bus without power.
  • Page 4 INSTALLATION - WIRING DIAGRAM continued FIGURE 3 NOTES DO NOT GROUND THE N2 BUS REFERENCE INSIDE THE ELECTRICAL PANEL. All N2 lines, including the shield should be insulated to prevent accidental contact to high voltage conductors. The N2 BUS cable should be mechanically secured where it enters the electrical panel. All N2 BUS devices should be connected together in a daisy-chain fashion.
  • Page 5 POINT MAP FOR H8026 ENERGY METER ENHANCED DATA STREAM, N2 PROTOCOL Johnson Controls N2 OPEN, "VND" TYPE UNITS POINT DESCRIPTION RANGE/VALUE NOTES 100A: 0.0025 kWH/count BI-1 is intended to be used as an accumulator (ACM) type, Consumption (Accum) 300A: 0.01 kWH/count it should not be read as a binary status.
  • Page 6 H8025 TYPICAL METASYS SETUP H8026 TYPICAL METASYS SETUP 1. Define a hardware object Define a hardware object Type ”N2 Device“, Device type: "VND" Type ”N2 Device“, Device type: "VND" 2. Add kWH Accumulator (Consumption) Point Add kWH Accumulator (Consumption) Point Directly map BI point 1 to an accumulator (ACM) object at Metasys.
  • Page 7: Address Selection Switches

    ADDRESS SELECTION SWITCHES Each device on the N2 BUS must have a unique address. These switches must be set to assign a unique address before the device is connected to the N2 BUS. If an address is selected which conflicts with another device on the N2 BUS, both devices will be unable to communicate. When setting the N2 BUS address, choose an address number which is not in use.
  • Page 8 METASYS CS MODEL FILES H8025.DDL H8026.DDL ********************************************************** ********************************************************** * Veris H8026, Energy Meter, Enhanced Data Stream Veris H8025, Energy Meter ********************************************************** ********************************************************** * This file contains two CS models to access all of the AI points * in the H8026. Two models are required because there are more @MODEL+ * than 16 AI points.
  • Page 9: Troubleshooting

    TROUBLESHOOTING SPECIFICATIONS Problem: STATUS LED does not blink. Specifications for H8025-xxxx-x Energy Transducer Input primary voltage ..................208 to 480 V AC Solution: Check fuses and voltage connections. STATUS LED should blink Number of phases monitored................... One or Three regardless of CTs, N2 BUS connections and DIP switch setting. Frequency........................

This manual is also suitable for:

Hawkeye 8026