H81xx

Product Identification

(cont.)

Specifications

Z205338-0F
Page 2 of 10
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
1.888.610.7664
Optional Comm Board (sold separately)
Model
H8163-CB
Modbus® Communications Board for H81xx Series
H8186-CB
BACnet® Communications Board for H81xx Series
H8126-CB
Metasys® N2 Communications Board for H81xx Series (consult factory if ordering this item)
Optional Accessory
Model
AH06
Mounting Bracket Kit (fits the Small, Medium, and Large CTs only)
H8150
H8163, H8167
Frequency
System Accuracy
Sample Rate
All Models
H8163 and H8167
PULSE OUTPUT
PULSE RATE
PULSE WIDTH
PHASE LOSS ALARM OUTPUT
Protection Class
Insulation Class
Operating Temperature Range
Storage Temperature Range
Humidity Range
Altitude of Operation
H8150
H8163, H8167
Agency Approvals
Installation Category
* Meters and current transformers are calibrated as a set. To achieve this accuracy, match the serial numbers on the current
transformers and the meter at the time of installation (does not apply to 100 A CTs).
** Do not apply 600V class current transformers to circuits having a phase-to-phase voltage greater than 600V without adequate
additional insulation between primary conductor and current transformers.
©2013 Veris Industrie
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
www.calcert.com
15
10
20
5
25
0
30
Description
Description
INPUTS
90 to 132VAC line-to-neutral
90 to 300VAC line-to-neutral
50/60 Hz
ACCURACY
±1% of reading from 2% to 100% of the CT current rating *
1280 Hz
OUTPUTS
1.2" x 3.8" (31 mm x 97 mm) viewing area, 160 segments, backlit LCD
N.O., Opto-FET, 100mA@24VAC/DC
0.10, 0.25, 0.50, 1.00 kWh per pulse (jumper selectable)
200msec closed
H8163: N.O. (opens on alarm, remains open while alarm persists);
H8167: N.C. (closes on alarm, remains closed while alarm persists);
Both H8163 and H8167: Opto-Fet, 100mA@24VAC/DC;
Fixed threshold 25% below any other phase
MECHANICAL
NEMA 1
600 VAC **
OPERATING CONDITIONS
0° to 50°C (32° to 122°F)
-40°C to 70°C (-40° to 158°F)
0-95% RH, non-condensing
0 to 2000 m
ELECTRICAL SERVICES
120/240 VAC with neutral, 208Y/120 VAC line-to-neutral
Any Wye service in which the phase L-N voltage is ≤300VAC and the phase-to-
phase voltage is ≤480 VAC nom. with neutral
COMPLIANCE INFORMATION
UL 61010
Cat III, pollution degree 2
sales@calcert.com
TM
09132