Installation Guide
Power Monitoring
H81xx
Installation (cont.)
Z205338-0F
Page 6 of 10
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
1.888.610.7664
5. Use color coding to attach current transformer (CT) leads to the input terminals (e.g. red labeled lead to red terminal). Polarity
is indicated in the wiring diagrams, but the meter is not polarity sensitive. See the Wiring section.
6. Use color coding to connect voltage leads to phase conductors (e.g. red transformer lead to red terminal). The meter is powered
from the monitored source, so connect the voltage leads to a circuit that is normally left on. See the Wiring section.
7. H8163 and H8167: Connect the output terminals to the control/data acquisition system. The Pulse Output is normally open. For
the H8163, the Phase Loss Output is normally open, and for the H8167, it is normally closed. Both are rated for 24 VAC/VDC@100
mA maximum. Ensure that the installation method and insulation ratings conform to local and national electrical codes.
Display
Plain
Full
Black
Black
Red
Yellow
Red
Yellow
+ - + - + -
N
A
B
C
+ A D + B D
+ C D
N
A
B
C
8. Set the backlight enabling jumper as desired. Remove the jumper to disable the backlight.
9. Set the Display Data jumper for either Plain or Full settings. Plain mode cycles the display through five data elements (kW, max.
kW since last reset, average PF, line-to-line voltage, and amps) for four seconds each. Full mode cycles through all of the data
available in the meter. See the Information Reporting section for more details.
©2013 Veris Industrie
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
www.calcert.com
15
10
20
5
25
0
30
Pulse Output
Phase Loss
Terminal
Output
Terminal
Backlight Enable Jumper
20 seconds per cycle
kW
max. kW
PF
Volts L-L
Amps
90 seconds per cycle
kW
max. kW
PF
Volts L-L
Amps
kVAR
kW Phase A
kW Phase B
kW Phase C
PF Phase A
etc.