oPeration

The H8030 and H8031 single-phase power transducers monitor energy parameters
from aggregate kW (demand) and kWh (consumption) to power factor. With two
platforms to choose from (Energy Only or Enhanced Data Stream), the applications
for the H8030/31 Series are diverse, including energy management, performance
contracting, demand limiting and cooling plant optimization.
The H8030/31 Series combines a microprocessor-based power meter and a high
accuracy split-core instrument-grade current transformer (CT) in a single unit.
Because the electronics are integral to the CT, and power can be monitored on up
to 63 loads using a single RS-485 drop, hardware and installation costs are greatly
reduced.

Product diagram

®
Enercept
3
4
5
6
1.
Voltage Leads: input range is 208 to 480VAC L-L.
2.
Fuses: maximum current draw 60mA. Fuses provided by the factory are rated 1/2A.
200 KAIC. Replace only with fuses of the same type and rating.
3.
Modbus connection port
4.
Status LED: blink codes: slow green for normal operation; slow red for incorrect
wiring or low power factor (less than 0.5); fast red for max. current exceedance.
5.
Address selection switch: set to assign an address prior to wiring.
6.
Fuse Pack
Z205220-0C
PAGE 2
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
H8030/8031
2
©2009 Veris Industries USA 800.354.8556 or 503.598.4564 / support@veris.com

installation

Disconnect and lock out power before installation.
1.
Choose a Modbus address not currently in use and set this address
using the Address Selection Switches on the bottom of the CT (see
Product Diagram).
2.
Connect the voltage leads to the conductors, at a location that is not normally
turned off. Connect voltage leads on the Line side of the conductor.
3.
Snap the CT onto the conductor.
If the application can exceed 20
1
times the rated CT current, use
wire ties to secure the I-bar to the
CT housing. This CT automatically
detects phase reversal, so CT
orientation is not important.
4.
Connect the RS-485 wires (observe polarity).
5.
For information regarding software setup, see the Modbus protocol specifications
available at www.veris.com/Modbus/
6.
Check power reading. Expected power:
kW = Volts x Amps x PF / 1000
kW = Horsepower x 0.746
ex.: 2.4 kW = 240 VAC x 10 Amps x 1.0 / 1000
INSTALLATION GUIDE
RS-485
STATUS
+
-
Shield
CONNECTION
MODBUS RS-485 LINE
To additional MODBUS Devices
ADDRESS
1
2
4
8
16
32
Wire tie
03095