Shutdown; Fault; Manual Current; Matrix Test - Xantrex PV225S-480-P Operation And Maintenance Manual

225 kw grid-tied photovoltaic inverter
Table of Contents

Advertisement

Shutdown

Fault

Manual Current

Matrix Test

Automatic Sleep Test

152607
The line interface controller is idle. The CCU2 monitors the status of the PV array
and utility grid, waiting in standby until the PV array is available to produce
power to the grid.
The PV225S has encountered a fault condition. When this happens, regardless of
the PV225S state of operation, the PV225S will stop processing all power and
execute an orderly system shutdown. A description of the fault and fault code will
appear on the operator interface LCD. The Fault state may be cleared from the
keypad once the cause of the fault has been corrected. See Chapter 4,
"Troubleshooting" for a complete description of all fault codes.
This operating state is provided to evaluate the existing PV array V-I
characteristics. The PV controller regulates a constant amount of PV current as
commanded by the user from the operator interface keypad, up to the PV current
limit of the PV225S. If the user commands more PV current than is available, the
DC bus voltage will drop below the minimum bus voltage level and the PV225S
will enter Shutdown mode.
This operating state is provided to verify proper operation of the matrices and
their associated control electronics. There is no power transfer between the PV
and utility in this mode. The O
PV225S to enter this state.
Toward the end of every solar day, the PV225S automatically determines when to
stop producing power dependent upon the output power of the inverter. As the net
output power of the PV225S nears zero, a timer is started to allow the inverter to
ride through any brief irradiance reductions.
N
FF
/O
switch must be in the O
Operating States
FF
position for the
2–5