Hardware reference
Label
Status
Description
ERH
off
Normal operation.
flashing
I/O size not configured.
on
Error detected in communication with controller.
NWST
off
Start-up error or fatal error detected.
single flash
TJ1-CORT in stopped state.
flashing
TJ1-CORT in pre-operational state.
on
TJ1-CORT in operational state.
BF
off
No network error detected.
1
single flash
Warning limit reached.
At least one of the error counters of the CAN controller has
reached or exceeded the warning level (too many errors).
2
double flash
A remote error or a heartbeat event has occurred.
3
flashing
Invalid configuration.
on
A duplicate node address has been detected, or
the unit is in Bus OFF state.
1. Single flash: one 200ms pulse, followed by 1 second off.
2. Double flash: two 200ms pulses, followed by 1 second off.
3. LED flashing frequency: 2.5 Hz.
3.9.3
Node number selectors
You can use the node number selectors to assign a node number to the TJ1-
CORT. This node number identifies the TJ1-CORT in the CANopen network.
The upper node number selector sets the tens of the node number. The
lower node number selector sets the units of the node number. Both
selectors range from 0 to 9. To set a selector to n, turn the arrow to point to
the label n.
The CANopen node number can range from 0 to 127. But the TJ1-CORT
only supports node numbers from 1 to 99. The default node number, 0, is
invalid. Therefore, the default node number must be changed before the
TJ1-CORT is used.