Lenovo ThinkSystem SR630 V2 Reference page 30

Hide thumbs Also See for ThinkSystem SR630 V2:
Table of Contents

Advertisement

Automatically notify Support: No
Alert Category: Critical - Fan Failure
SNMP Trap ID: 11
CIM Prefix: PLAT CIM ID: 0480
User Action:
Complete the following steps until the problem is solved:
1. Reseat the failed fan reported.
2. Install the fan into another known good fan slot to see if the issue is resolved.
3. If the problem persists, collect service data log from the XCC WebGUI and replace the fan.
4. Contact Lenovo Support.
• FQXSPCA0007J: Numeric sensor [NumericSensorElementName] going high (upper non-critical)
has asserted.
This message is for the use case when an implementation has detected an Upper Non-critical sensor
going high has asserted.
Severity: Warning
Serviceable: Yes
Automatically notify Support: No
Alert Category: Warning - Temperature
SNMP Trap ID: 12
CIM Prefix: PLAT CIM ID: 0490
User Action:
Complete the following steps until the problem is solved:
1. Check the XCC event log for any fan or cooling related issues and address them first.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are
correctly installed in place and keep clean.
3. Make sure that the room temperature meets operating specifications.
4. Upgrade all system firmware and chassis firmware (if applicable) to the latest level.
5. If the problem persists, collect service data log from the XCC WebGUI and contact Lenovo Support.
• FQXSPCA0009M: Numeric sensor [NumericSensorElementName] going high (upper critical) has
asserted.
This message is for the use case when an implementation has detected an Upper Critical sensor going
high has asserted.
Severity: Error
Serviceable: Yes
Automatically notify Support: No
Alert Category: Critical - Temperature
SNMP Trap ID: 0
CIM Prefix: PLAT CIM ID: 0494
User Action:
Complete the following steps until the problem is solved:
1. If the sensor is "Ambient Temp":
a. Make sure the data center Temperature environment is within 47°C degree.
b. Make sure there is no hot air in front of the affected system.
26
ThinkSystem SR630 V2 Messages and Codes Reference