TEMPERATURE CONTROL ADJUSTMENT FOR
HIGH ALTITUDE ONLY!
TERMS:
Cut-out - Temperature sensed
by the controller that shuts the com-
pressor off.
Cut-in - Temperature sensed
by the controller that turns the com-
pressor on.
REQUIRED TOOLS
• Phillips Head Screwdriver
• 5/64" or 2 mm Allen Wrench
• T-7 Torx Wrench
STEP 1
Unplug the cooler.
STEP 2
Remove the screws that secure the
temperature control to the inset box
lower left side of the cabinet (when
facing the front
of the cabinet).
STEP 3
Pull out gently from cabinet.
NOTE:
Mechanical temperature
controllers are affected when
functioning at high altitude.
The cut-in and cut-out
temperatures will be colder
than when the controller
functions closer to sea level.
12
INSTALLATION / OPERATION INSTRUCTIONS
STEP 4
For high elevation installations,
it may be necessary to "warm-up"
the set points. To make the adjust-
ment, insert the appropriate tool in
each adjustment screw and turn 1/4
of a revolution clockwise (to the
right). This procedure will adjust
both the cut-in and cut-out about
2°F warmer.
STEP 5
Make sure to reconnect the pink
wire to the proper spade
terminal when reinstalling.
Danfoss Temperature Control (High Altitude Adjustment Only!)
............ www.truemfg.com ............
True Food Service Equipment, Inc.
Cut-out Adjustment Screw Allen (5/64"
or 2 mm) (clockwise for warmer)
Cut-in Adjustment Screw Torx (T-7)
(clockwise for warmer)
Compressor Connection (pink)
Compressor Connection (pink)