Connecting The Power Cable - KSB Calio Pro Installation & Operating Manual

High-efficiency circulator pump
Table of Contents

Advertisement

Earth leakage circuit
breaker
Table 8: Power cable dimensions
Power cable dimensions
Outside diameter
Cross-section
3
Fit wire end sleeves on stranded / flexible electric cables.
5 Installation at Site
DANGER
Incorrect connection to the mains
Danger of death from electric shock!
▷ Observe the technical specifications of the local energy supply companies.
▷ The core cross-section has to be at least 3 × 0.75 mm
▷ Use a slow acting circuit breaker of at least 1.4 × the nominal current of the
pump set. For the nominal current see name plate.
▷ The power cable has to be fitted with an all-pole isolating switch with a
minimum contact opening of 3 mm. A shockproof plug must not be used.
▷ If the power cable of the device is damaged, have it replaced by the
manufacturer, a customer service technician or a similarly qualified person. See
EN 60335-1.
NOTE
Using a permanently installed power cable of type H05VV-F 3G1.5 or similar is
recommended.
Using a universal AC/DC sensitive residual current device to DIN VDE 0160 is
recommended. Conventional residual current devices might either fail to trip or trip
erroneously.
Discharge current per pump < 3.5 mA

5.6.1 Connecting the power cable

1. Verify the supply voltage at the site against the data on the name plate.
2. Switch off the power supply and make sure it cannot be switched on again
unintentionally.
3. Fit the union nut and joint ring on the power cable.
4. Guide the power cable through the plug housing until the cable ends are freely
accessible.
5. Strip the power cable as shown in the illustration.
Strip about 18 mm of the earth conductor sheath. Strip about 13 mm of the
neutral conductor sheath and L conductor sheath.
Strip 6 mm of each core's sheath as a minimum.
Fig. 9: Stripping the power cable [mm]
6. Connect the cores at the contact insert.
Calio Pro / Calio Pro Z
Values
5,5 - 8,0 mm
2
0,75 - 1,5 mm
(solid or stranded
2
.
3)
)
27 of 62

Advertisement

Table of Contents
loading

This manual is also suitable for:

Calio pro z

Table of Contents