Setting Airflow

With all ductwork connected and a clean filter in place, measure the
External Static Pressure (ESP) of the unit in locations below. Use the
appropriate airflow table for the furnace and outdoor unit installed.
Measurements must be made prior to the evaporator coil, if equipped,
and after the filter.
Model
L8X1B060U3PXAA
E E x x a a m m p p l l e e 1 1 : : S S 8 8 B B 1 1 ( ( D D e e f f a a u u l l t t T T a a p p 7 7 ) )
Cooling / HP
2 Ton Single Stage Outdoor
40
Furnace Airflow (CFM) Vs. External Static Pressure (in. W.C.)
Tap
SCFM
1
Watts
SCFM
2
Watts
SCFM
3
Watts
SCFM
4
Watts
SCFM
5
Watts
Clean
Filter
0.1
0.3
829
689
83
95
1087
985
163
179
1210
1126
211
228
1238
1157
227
244
1481
1409
381
399
Total ESP = 0.7" W.C.
Required Airflow = 1400 cfm (4T x 350 cfm/ton)
New Tap Number = Tap 6
Evaporator
Coil
0.5
0.7
549
410
107
119
884
782
195
210
1043
959
245
262
1076
995
261
278
1338
1266
417
435
18-CE07D1-1C-EN
0.9
270
130
681
226
876
279
914
295
1195
453