Setting Airflow

With all ductwork connected and a clean filter in place, measure the
External Static Pressure (ESP) of the unit in locations below. Use the
appropriate airflow table for the furnace and outdoor unit installed.
Note: See Airflow Tables section in this document.
Measurements must be made prior to the evaporator coil, if equipped,
and after the filter.
Note: Check out fieldtechhelp.com and search for "Setting Air Flow on
the 9-Tap Motor" to watch a short video.
Model
S8B1B080M4PS
S8X1B080M4PS
S8X2B080M4PS
This is an Example Airflow Table only. See
(a)
Exapmple 1, 2
(b)
Example 1
(c)
Example 2
Example 1: S8X2B080M4PS (Default Tap 7)
Cooling / HP
3 Ton Single Stage Outdoor
Total ESP = 0.7" W.C.
Required Airflow = 1050 cfm (3T x 350 cfm/ton)
New Tap Number = Tap 4
Example 2: S8X2B080M4PS (Default Tap 3 & 7)
4 Ton Two Stage Outdoor
56
Furnace Airflow (CFM) Vs. External Static Pressure (in. W.C.)
Tap
0.1
1
633
2
957
3
1220
4
1403
5
1524
6
1684
7
1700
8
1858
9
1967
"Airflow Tables," p. 20
Clean
Filter
0.3
0.5
297
800
719
1080
940
1298
1192
1428
1336
1574
1544
1625
1551
1790
1723
1898
1829
for complete Airflow data.
nd
Total 2
Stage ESP = 0.9" W.C.
st
Total 1
Stage ESP = 0.6" W.C.
Required 2
cfm/ton)
Required 1
airflow x .75)
nd
New 2
Stage Tap Number = Tap 7 (no change)
st
New 1
Stage Tap Number = Tap 4
0.7
428
800
1087
(a)
1248
1401
1476
(b)
1656
1760
nd
Stage Airflow = 1400 cfm (4T x 350
st
Stage Airflow = 1050 cfm (2