floor and the Furnace must be located or protected
to avoid physical damage from vehicles.
9. The gas furnace must not be located where
excessive exposure to contaminated combustion
air will result in safety and performance related
problems. Avoid the following known
contaminants:
a. Permanent wave solutions
b. Chlorinated waxes and cleaners
c. Chlorine based swimming pool chemicals
d. Water softening chemicals
e. De-icing salts or chemicals
18-CE07D1-1C-EN
F F u u r r n n a a c c e e I I n n s s t t a a l l l l a a t t i i o o n n G G u u i i d d e e l l i i n n e e s s
f.
Carbon tetrachloride
g. Halogen type refrigerants
h. Cleaning solvents (such as
perchloroethylene)
i.
Printing inks, paint removers, varnishes, etc.
j.
Hydrochloric acid
k. Cements and glues
l.
Antistatic fabric softeners for clothes dryers
m. Masonry acid washing materials