Setting Airflow - Trane A801X026AM2SC Installation, Operation And Maintenance Manual

Upflow/downflow/horizontal left/right gas-fired, single stage induced draft furnaces with high efficiency motor
Table of Contents

Advertisement

Setting Airflow

With all ductwork connected and a clean filter in place, measure the
External Static Pressure (ESP) of the unit in locations below. Use the
appropriate airflow table for the furnace and outdoor unit installed.
Note: See Airflow Tables section in this document.
Measurements must be made prior to the evaporator coil, if equipped,
and after the filter.
Note: Check out fieldtechhelp.com to watch a short video.
Model
A801X080BM4S
This is an Example Airflow Table only. See
E E x x a a m m p p l l e e 1 1 : : A A 8 8 0 0 1 1 X X ( ( D D e e f f a a u u l l t t T T a a p p 7 7 ) )
Cooling / HP
4 Ton Single Stage Outdoor
A801X-SVX001-1A-EN
Furnace Airflow (CFM) Vs. External Static Pressure (in. W.C.)
Tap
0.1
1
633
2
957
3
1220
4
1403
5
1524
6
1684
7
1700
8
1858
9
1967
"Airflow Tables," p. 16
Clean
Filter
0.3
0.5
297
800
719
1080
940
1298
1192
1428
1336
1574
1544
1625
1551
1790
1723
1898
1829
for complete Airflow data.
Total ESP = 0.7" W.C.
Required Airflow = 1400 cfm (4T x 350 cfm/ton)
New Tap Number = Tap 6
Evaporator
Coil
0.7
0.9
428
213
800
660
1087
981
1248
1164
1401
1337
1476
1401
1656
1589
1760
1691