Table Of Internal Humidifier Alarms With Cpy Control - Mitsubishi Electric s-MEXT-G00 006 Technical Manual

Computer room air conditioner
Table of Contents

Advertisement

TM_s-MEXT_ME28relC_00_12_19_EN
2.8.2

Table of internal humidifier alarms with CPY control

The internal humidifier alarms managed by the CPY control are transmitted by the CPY control to the EVOLUTION+ controller via the serial line.
The CPY control alarm codes are grouped below for each alarm that is read by the controller.
EVOLUTION+
Code
Display description
Humidifier Board
195
Offline
Life timer expired
402
Reset/Clean cylinder
Humidifier:
404
Drain alarm
Humidifier:
406
Loss of Water
Humidifier:
408
Low Current
Humidifier:
410
High Current
Generic alarm
412
Humidifier
Room Humidity
540
Below Min. Limit
Room Humidity
541
Above Max. Limit
Differently from alarms, warnings forwarded by the CPY to the EVOLUTION+ controller are not grouped into notifications, but can only be displayed in the internal humidifier
dedicated mask.
CPY warnings
Code
0
1
2
3
4
5
Refer to the CPY manual for further info.
Technical manual
CPY alarms
Type
Code
Al-Auto
1
Al-Auto
3
Al-Auto
12
Al-Auto
11
Al-Auto
8
4
Al-Auto
7
2
5
Al-Auto
6
9
10
S-Auto
S-Auto
Description
No warning
CY: Maintenance warning
EA: Foam present
CP: Cylinder depletion forewarning
CL: Depleted cylinder
E2: Damaged Eeprom
Red indicator LED
Description
2 slow flashes
Device Offline
8 fast flashes
Mn - Cylinder life
5 slow flashes
Ed - Drain alarm
3 slow flashes
EF - Missing water
4 slow flashes
EP - Low production
5 fast flashes
EC - High conductivity
2 fast flashes
EH - High current
I64/I82 val. Incorrect
4 fast flashes
E1 - Params not dwnld
3 fast flashes
E0 - Calib.Par. not ok
8 slow flashes
EU - Full cylinder
7 slow flashes
E3 - Probe not conn.
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
68