Mitsubishi Electric s-MEXT-G00 006 Technical Manual page 36

Computer room air conditioner
Table of Contents

Advertisement

TM_s-MEXT_ME28relC_00_12_19_EN
Mask of the terminal
--------------- P26.05
Units in stand-by
in LAN:
--------------- P26.06
Stand-by mode limits
in LAN status:
--------------- P26.11
H&L Local Temp prot.
enable :
--------------- P26.12
Diff. for On with High
local temp :
02.0°C
--------------- P26.13
Diff. for On with Low
local temp :
02.0°C
--------------- P26.14
Time before Off
protection with T.room
in range:
300s
--------------- P26.15
Time before On
protection with T.room
out of range:
060s
--------------- P26.16
Active Fan on Stand by
Enable:
--------------- P26.17
Active fan speed: 070%
--------------- P26.18
Active Pressure Load
enable:
--------------- P26.19
Disable APL during
Diff.P probe alarm:
--------------- P26.20
H&L Local Press. prot.
enable :
--------------- P26.21
Diff. for On with High
local press:
010Pa
--------------- P26.22
Diff. for On with Low
local press:
010Pa
--------------- P26.23
Time before Off
protection with local
DeltaP in range: 300s
--------------- P26.24
Time before On prot.
with local DeltaP
out of range:
060s
Technical manual
Description
Parameter for configuring the number of units in stand-by in LAN (0 1 unit - 1 2 units) and for configuring the
Stand-by mode limits in LAN function (N:disabled - Y:enabled)
2
Y
Parameter for enabling Hot&Cold spot management
Parameter for configuring the differential according to the average temperature for activation of the Hot Spot
N
function
Only visible for units with adjustment according to average temperature
Parameter for configuring the differential according to the average temperature for activation of the Cold Spot
function
Parameter for configuring the time for deactivation of the Hot & Cold Spot function
Parameter for configuring the time of activation of the Hot & Cold Spot function after exceeding of the limits
Parameter for enabling the Active Fan on Standby function
N
Parameter for setting the fan speed during operation in Active Fan on Standby mode
Enable the Active Pressure Load function (APL).
Enable disabling of the APL function during the air differential pressure probe alarm.
N
Only visible for units with air flow control according to DeltaP enabled
N
Parameters for setting
Hi & Low local pressure protection function enable
N
On differential for floor pressures above average
Parameters for setting
On differential for floor pressures below average
Time before stopping protection in case of local pressure differences within the limits
Parameter for setting the time delay before the start of the protection in case of local pressure differences outside
the limits
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
36
N. Par.
26.05
26.06
26.11
26.12
26.13
26.14
26.15
26.16
26.17
26.18
26.19
26.20
26.21
26.22
26.23
26.24