Input/Output Configuration Table; Main Controller - Mitsubishi Electric s-MEXT-G00 006 Technical Manual

Computer room air conditioner
Table of Contents

Advertisement

TM_s-MEXT_ME28relC_00_12_19_EN
17

INPUT/OUTPUT CONFIGURATION TABLE

17.1

MAIN CONTROLLER

s-MEXT-G00
pCO size
Circuits
Analogue Inputs
Connector
Type
Description
U1
4-20mA
Circuit 2 evaporation pressure transducer
J2
U2
NTC
Ambient air temperature
U3
NTC
Delivery air temperature
U4
4-20mA
Evaporation pressure transducer
J3
U5
/
Remote on/off
Free
0
Connector
Type
Description
ID1
/
Phase Sequence
ID2
/
Air flow differential pressure switch
ID3
/
Clogged filter differential pressure switch
ID4
/
Heater thermostat
J5
ID5
/
Fire / Fumes sensor
ID6
/
Flooding sensor
ID7
ID8
/
Gas leak sensor
Free
1
Notes:
(1) in case of unit with two circuits
Technical manual
Digital Inputs
Small
Connector
1-2
Fieldbus 2
Fieldbus 2
Fieldbus 1
Fieldbus 1
Fieldbus 1
Fieldbus 1
Fieldbus 1
Connector
Y1
(1)
Y2
J4
Y3
Y4
Free
Connector
NO1
J12
NO2
NO3
NO4
J13
NO5
NO6
J14
NO7
J15
NO8
Free
102
Fieldbus
Address
Description
21
PAC-IF 013B-E Master
22
PAC-IF 013B-E Slave 1
1
Gavazzi CPT network transducer
8
pCOe 1 expansion board
128
Room T+H probe
129
Remote T+H probe
148
CPY humidifier card
Analogue Outputs
Type
Description
0-10V
Internal Electronic Fan
DC
3
Digital Outputs
Type
Description
/
Internal Fan + Delivery Damper
/
Heating element 1
/
Heating element 2
/
Alarm A
/
Alarm B
3