Mitsubishi Electric s-MEXT-G00 006 Technical Manual page 41

Computer room air conditioner
Table of Contents

Advertisement

TM_s-MEXT_ME28relC_00_12_19_EN
Mask of the terminal
----------------P27.22
Minimum temp. for cool
compensation:
00.0 °C
----------------P27.23
Maximum temp. for cool
compensation:
10.0 °C
----------------P27.24
Maximum cool setpoint
compensation:
00.0 °C
----------------P27.25
Minimum temp. for heat
compensation:
00.0 °C
----------------P27.26
Maximum temp. for heat
compensation:
10.0 °C
----------------P27.27
Maximum heat setpoint
compensation:
00.0 °C
Regulations
2
Regulation 2 parameter
NOT Available
User
Password:
0000
Serial
--------------- P30.01
Enable supervision:
Y
Technical manual
Description
Parameters for setting
Offset start time (cooling)
Offset end time (cooling)
Parameter for setting the maximum setpoint offset (cooling)
Parameters for setting
Offset start point (cooling)
Offset end point (Cooling)
Parameter for setting the maximum setpoint offset (heating)
Access mask to Regulations submenu 2. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the
submenu.
It informs that no parameters are available in the menu for the unit.
Access mask to "User" menu. Enter the "User" password for access.
Access mask to BMS management submenu. Press "Up" or "Down" to scroll the other masks and "Esc" to return
to the submenu.
Supervision presence configuration parameter
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
41
N. Par.
27.22
27.23
27.24
27.25
27.26
27.27
30.01

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

S-mext-g00 044

Table of Contents