TM_s-MEXT_ME28relC_00_12_19_EN
Mask of the terminal
--------------- P20.06
Inv. compressor reg.
intergral time:
900s
--------------- P20.07
Inv. compressor reg.
derivative time: 000 s
--------------- P20.08
Dirty filters sensor
presence:
--------------- P20.09
Fire/smoke sensor
presence:
--------------- P20.10
Flooding sensor
presence:
--------------- P20.13
Remote ON/OFF
presence:
--------------- P20.18
Regulation band in
cooling:
2.0°C
--------------- P20.19
Regulation band in
heating:
1.5°C
--------------- P20.20
Regulation band for
dehumidif.:
5%RH
--------------- P20.21
Regulation band for
humidification:
5%RH
--------------- P20.22
Integral time reg.
humidifier
900s
--------------- P20.23
Derivative time reg.
humidifier
000s
--------------- P20.24
Cooling set point
lower limit:
24.0°C
--------------- P20.25
Cooling set point
upper limit:
32.0°C
Technical manual
Description
Parameter for setting
Integral adjustment time
Parameter for setting the inverter compressor adjustment derivative time (units with inverter compressor)
Parameter for configuring the dirty filters sensor (N:disabled - Y:enabled)
and for configuring the fire smoke sensor (N:disabled - Y:enabled)
N
N
Parameter for configuring the flooding sensor (N:disabled - Y:enabled)
N
Parameter for configuring the ON/OFF remote contact (N:disabled - Y:enabled).
N
Parameter for setting the cooling regulation band and the heating regulation band
Parameter for setting the dehumidification regulation band and the humidification regulation band
Parameter for setting the Humidification integral time (PID)
Humidification regulation derivative time (PID)
Parameter for setting the Lower setpoint cooling limit and the Upper cooling setpoint limit
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
28
N. Par.
20.06
20.07
20.08
20.09
20.10
20.13
20.18
20.19
20.20
20.21
20.22
20.23
20.24
20.25