Parameter Table - Mitsubishi Electric s-MEXT-G00 006 Technical Manual

Computer room air conditioner
Table of Contents

Advertisement

TM_s-MEXT_ME28relC_00_12_19_EN
2.7.3

Parameter Table

The numbering of the parameters is divided by menu.
1x corresponds to a submenu of the "Factory menu"
2x corresponds to a submenu of the "Service menu"
30 corresponds to a submenu of the "User" menu.
50 corresponds to the "Setpoint" menu.
The following table lists the controller parameters and the relative maximum and minimum values.
N. Par.
Description
10.10
Internal fan project speed
10.16
Start scale value of differential pressure transducer
10.17
End scale value of differential pressure transducer
10.30
Start scale value of low pressure transducer
10.31
End scale value of low pressure transducer
10.22
Initial logo [Mitsubishi - RC]
10.26
High part serial number of unit
10.27
Medium part serial number of unit
10.28
Low part serial number of unit
10.32
Number of PAC-IF013B-E
10.33
Minimum Mr. Slim OFF time
11.01
Configuration of air flow control type [0: Disabled | 1: Flow | 2: DeltaP]
11.02
Number of EC fans
EC fan diameters [0: dn355 | 1: dn500 | 2: dn630 | 3: dn500PL | 4: dn310 Vpro-ZH | 5: dn500 Vpro-ZH | 6:
dn560 Vpro-ZH | 7: dn630 Vpro-ZH | 8: dn630PL | 9: dn710 Cpro-ZH | 10: dn255 | 11: dn310 | 12: dn400 |
11.03
13: dn450 | 14: dn560]
12.01
Minimum compressor ON time
12.02
Minimum compressor OFF time
12.03
Minimum time between two ON's of the same compressor
13.05
Electronic valve configuration [0: Disabled | 1: Enabled]
14.03
Sensors alarm delay
14.04
Low pressure alarm delay
14.08
Constructor cold setpoint minimum limit
14.09
Timed dehumidification control enable [0: Disabled | 1: Enabled]
14.10
Minimum settable room temperature value for disabling dehumidification
14.11
Maximum dehumidification cycle ON time
14.12
Minimum delay for new dehumidification cycle
14.13
Enabling of air flow reduction in dehumidification for direct expansion unit with dehumidification active
14.14
Maximum manual operation time
20.01
Regulation probe configuration [0: Return | 1: Delivery]
20.02
Fan start delay after power on
20.03
Ventilation modulation start delay
20.04
Ventilation adjustment start delay
20.06
Integral adjustment time (units with inverter)
20.07
Inverter compressor adjustment derivative time (unit with inverter)
20.08
Dirty filter sensor configuration [0: Disabled | 1: Enabled]
20.09
Smoke sensor configuration [0: Disabled | 1: Enabled]
Technical manual
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
57
Default
U.M.
Min.
70
%
0
0
Pa
0
100
Pa
0
0.0
bar
0.0
30.0
bar
0.0
5
-
0
32
-
1
0
-
0
0
-
0
1
-
1
120
S
1
0
-
0
1
-
1
0
-
0
60
s
60
60
s
60
360
s
360
0
-
0
60
s
5
180
s
2
10.0
°C
10.0
0
-
0
22.0
°C
18.0
10
min
5
3
min
3
0
-
0
1800
s
0
1
-
0
0
s
0
120
s
0
50
s
20
900
s
0
0
s
0
0
-
0
0
-
0
Max.
100
1000
5000
2.0
10.0
5
999
999
999
2
999
2
5
14
600
600
999
1
999
999
30.0
1
30.0
15
20
1
3600
1
999
500
999
999
999
1
1